If 1/100 is selected, there are 2 decimals in the output value, the max value is 327.67, and there are 0 deci-
mals if 1/1 is chosen, then the max value is 32767.
3. Selected curve
This graph shows the curve for the values in the Configurable Curve table (item 4).
4. Configurable curve
In this table it is possible to type the relation between input 0-10 V and output kW 1/10 in this example.
As seen in the table, the input ranges from 0-5 V, and the output is 0.0-1.0 kW. If the input voltage goes
above 5 V, the output will stay at 1.0 kW.
5. Wire-break detection
If the input signal is outside of configured range, the wire fail detection is activated. It depends on the input
type working area of the sensor whether open circuit and short circuit failures will be detected. Read more
about this in the chapter about wire fail detection.
6. Alarm setup
It is possible to set two alarms, and the related settings are the same as for regular inputs on the AGCs. The
selected set point relates to the output value. In this example, the output value is 0-1 kW, and the first alarm
activates when the value has been above 0.7 kW in 1 second.
4.3.2 Thermocoupler with cold junction compensation
The CIO 308 module compensates for the cold junction. This can be done with the internal temperature
measurement if the thermocoupler is connected to the CIO 308 module terminals.
CIO 308 installation and commissioning
guide 4189341078 UK
I/O setup