2.4.3 CAN bus
The CIO module(s) can be configured as the only device on the CAN bus or together with an engine control-
ler (ECU) on the same CAN bus as shown in the below example. CIO module(s) can be placed together with
all the different engine protocols which are available in the AGC (both J1939 and CANopen), because the
CIO module will adapt to the baud rate on the CANline.
It is possible to connect up to three CIO modules of each type to one AGC.
A controller cannot have both CIO modules and Beckhoff modules connected
Below is an example that shows how the CAN bus can be connected:
AGC
CAN bus
H GND L
ECU
CAN bus
H GND L
CIO
CAN bus
H GND L
120
S1=ON
AGC 200
On the AGC 200, only CAN port C is available
Terminal
Function
Desctiption
13
CAN H
CAN port C
14
Com
15
CAN L
AGC-4/AGC Plant Management
On the AGC-4 and AGC Plant Management, it is possible to use the CAN ports C, D, E or F, and you need to
have at least one of the following options: H5, H8 or H12.
CIO 308 installation and commissioning
guide 4189341078 UK
Installation, mounting and wiring
DEIF A/S