Evaluation table for...
DEHNguard S/M,
Protection module
Type
Part No.
DG MOD 275
952 010
386
474
DG MOD 75
952 011
107
133
DG MOD 150
952 012
215
265
DG MOD 320
952 013
458
562
DG MOD 385
952 014
557
683
DG MOD 440
952 015
643
787
DG MOD 600
952 016
869
1063
DG MOD 48
952 018
66
84
DG MOD NPE
952 050
397
604
DGP C MOD
952 060
397
604
Tolerance range
Note
:
The module has to be removed for testing
(measuring)!
Note
:
The module has to be removed for testing
(measuring)!
DEHNgap,
Protection module
Type
Part No.
T C 255
900 134
397
604
T C H 255
900 216
496 856
T C G 255
900 219
397
604
Tolerance range
EX spark gap
Type
Part No.
EXFS 100
923 100
600
1000
EXFS 100 KU
923 101
600 1000
Tolerance range
Page
25
LLV
in [ V ]
ULV
in [ V ]
LLV
in [ V ]
ULV
in [ V ]
LLV
in [ V ]
ULV
in [ V ]
Note:
The spark gap may only be tested (measured) after
removing it from the installation and outside of the Ex
zone.