Publication No. 1637/ UPDATE
07
.1
9
Mat-No. 3003103
5
PVC outer sheath
Colour
Dark grey
(similar to RAL 7000)
Equivalent separation
Air
≤
45 cm
distance
Solid material
≤
90 cm
Outer diameter
Dark grey sheath
20 mm
Black sheath
17 mm
Minimum bending radius
200 mm
Permanent temperature range
(in case of fixed installation)
-30° to +70°C
Ambient and conductor temperature -5°C to +40°C
(during installation and processing)
Maximum tensile load
950 N
Inner conductor (copper)
19 mm²
Used in case of class of LPS (if
k
c
=1)
II, III, and IV
Tested with I
imp
based on
EN 62561-1
150 kA (10/350 μs)
Chemical properties
Reaction to fire, self-extinguishing
Yes
Weather-proof (UV-stabilised)
Yes
Fire load
3.19 kWh/m
Table 1
Technical data of
HVI
light Conductors
solid copper conductor,
19 mm²
outer sheath
(dark grey)
semiconductive sheath
insulation layer