DEGA UPA III Скачать руководство пользователя страница 9

 

5.

 

Malfunction 

If a malfunction should occur, the LCD displays the measured values, an error code and also a key symbol 

. The 

meaning of individual error codes can be found in the attachments. 

6.

 

Monitoring the calibraton periods 

After  12  months  since  the  last  calibration  (Max.  calibration  interval)  an  inscription 

  starts  flashing  on  the  LCD 

display. The connected transmitters must be calibrated immediately.

 

7.

 

Reading the record of measured concentrations and alarms 

The controller periodically after 60s stores the current detected concentration into it's internal memory. The internal memory 
retains data from the last 49 000 measurements (cca 34 days). In order to read this information, the program DegaConfig is 
required. Refer to the DegaConfig program instruction

 

8.

 

Indication of past alarms 

The controller is equipped with an indication of alarms that have already faded. If such an alarm occurred, the icon 

 is 

displayed. To view these alarms, enter the menu HIST 

 HILA, where the date and time since the highest measured alarm 

since reseting HIST 

 _RST is displayed for each transmitter. After viewing the history it's possible to reset the counter 

throught HIST 

 _RST and the icon 

 disappears. 

9.

 

Automatic adjustment of the 0 point 

The connected digital transmitters have an inner diagnostic, which detects whether or not the 0 point is in disbalance. If so, an 

automatic adjustment will take place and the controller indicates this with the icon 

10.

 

Menu 

Enter the menu by pressing the ENTER button and hold it for cca 5s. The main segments of the LCD display the menu 
functions. Use the arrows to move from one entry to another and press ENTER for selecting an entry. The last entry is always 
EXIT, which returns you to a higher menu level. The menu stucture is as follows: 

 

↓ 

← 

↑ 

submenu 

HIST 

 

 

INFO 

 

 

CONF 

 

 

TEST 

 

 

SERV 

 

 

EXIT 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI1H 

 

NCAL 

 

TMP1 

 

RELE 

 

SERV 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI8H 

LCAL 

TMP2 

TRAN 

SERV 

 

 

 

 

 

 

 

 

HI12 

TEMP 

ALM1 

_RST 

EXIT 

 

 

 

 

 

 

 

 

 

 

HI24 

ADDR 

ALM2 

EXIT 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI2D 

EXIT 

 

ALM3 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI7D 

 

 

ALM4 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIAL 

 

 

CALI 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HILA 

 

 

EXIT 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

_RST 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXIT 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 

Содержание UPA III

Страница 1: ...ny form without the prior permission of DEGA CZ s r o is prohibited DEGA CZ s r o reserves the right to alter the specifications of the hardware and software described in this manual at any time and without prior notice DEGA CZ s r o bears no liable for any damage resulting from use of this device ...

Страница 2: ... past alarms 9 9 Automatic adjustment of the 0 point 9 10 Menu 9 History Menu HIST 10 Information menu INFO 10 Configuration menu CONF 10 Controller testing menu TEST 11 Service Menu SERV 11 Maintenance 12 1 Operation Maintenance 12 2 Replacement of the battery 12 Attachments 13 1 Table of error codes 13 General warranty terms and conditions 14 For your safety Beware of static electricity Electron...

Страница 3: ... 25 mm max 100 m Cable for connecting signalization a pushbutton cable 2 x 1mm Output USB for PC configuration RS485 protocol DEGA or MODBUS on request for the host system PLC PC 10x switching relays 250 V 10 A 2x outupt for visual and acoustic alarms max load see chapter Assembling and connecting the wiring paragraph 6 Communication speed of RS485 9 6 kB Functional safety EN61508 SIL 1 Dimensions...

Страница 4: ...e suppy voltage 22 26V Terminal block relay RE8 RE10 Fuse T400mA Auxiliary input output 24V DC Power supply terminal block 230VAC Temperature sensor terminal block Acoustic alarm lay key terminal block Flooding sensor terminal block Acoustic alarm terminal block Bus temrinal block 1 for digital transmitters Bus temrinal block 0 for digital transmitters RS485 for the host system Analog inputs Optic...

Страница 5: ...e cover of the case and lock the controller by using the handle 2 Connecting a transmitter via current loop Connect one transmitter on each channel of the controller 3 Connecting a transmitter via RS485 It is possible to connect up to 16 transmitters on each controller input depending on their electrical distance from the controller Wiring installation for RS485 Wiring must be done using bus topol...

Страница 6: ... the supply voltage and the maximum current load Supply voltage 230V AC The highest current load of the controller is 1 4A This current serves to power the connected transmitters and the visual and acoustic alarms which are connected to the terminal blocks LIGHT_SIG and SOUND_SIG Example There are 4 transmitters connected to the controller with a consuption of 60 mA each The remaining 1 16 A I 140...

Страница 7: ...imru můžeme regulovat výstupní napětí zdroje v rozsahu 22 26V V případě že jsou snímače připojeny na velkou vzdálenost může být pro správnou funkci nutné zvýšit napájecí napětí Controls The control panel is equipped with a segmented LCD display and can be controlled using the LEFT RIGHT and ENTER buttons In Basic mode the controller displays the concentration and the states of the configured chann...

Страница 8: ...cation or an evnetual sensor malfunction If the displayed channel is digital 1 to 32 the adress of the connected sensor is also displayed Connected analog transmitters have a range of 41 to 48 The controller sequentially switches the configured channels in a 3s interval If we want to select a transmitter manually we can do so with the buttons LEFT and RIGHT The status of the sensor bundled with an...

Страница 9: ...larm occurred the icon is displayed To view these alarms enter the menu HIST HILA where the date and time since the highest measured alarm since reseting HIST _RST is displayed for each transmitter After viewing the history it s possible to reset the counter throught HIST _RST and the icon disappears 9 Automatic adjustment of the 0 point The connected digital transmitters have an inner diagnostic ...

Страница 10: ...n to return the the history menu Note In case of equipping a larger quantity of transmitters the loading of the history may take a few seconds Information menu INFO NCAL Displays the date of the next transmitter calibration LCAL Displays the date of the calibration TEMP Displays the temperature of the DEGA Tc II sensor ADDR Displays the controller address on the RS485 HOST bus EXIT Returns to a hi...

Страница 11: ...nged with LEFT and RIGHT and using ENTER will confirm the selection In the final part of this whole process select either YES for saving the values into the transmitters or no for finishing the calibration without saving the values Controller testing menu TEST RELE Setting the relay output TRAN Simulation of the measured values _RST Controller restart EXIT Returns to a higher menu level The entry ...

Страница 12: ...required accuracy and the occurrance of disturbing gases in the atmoshpere Also carry out a functional control 1 x every three months checking the function of the entire detection system using a test gas which does not exceed the range of the sensor We recommend using gas intended for laboratory use For the functional control do not use means for testing fire alarm detectors Perform calibration on...

Страница 13: ... error contact the manufacturer X SEN MISM The set sensor ID does not match with the connected sensor Checking the configuration of the sensor required X ELFAILED EL sensor test error Sensor error only informative subsides by itself X X HEATING Transmitter is in preheating mode Wait a few minutes the transmitter will automatically enter measurement mode X EE25 ERR Error reading the internal FLASH ...

Страница 14: ...ct shall be replaced 616 paragraph 4 of the Commercial Code 6 The buyer who exercises the right of warranty repair is not entitled to the return of the parts that have been replaced 7 The warranty period can be extended for up to 48 months and its validity can be extended beyond the standard length on the basis of the conclusion of an individual warranty contract Further information may be obtaine...

Отзывы: