DEGA UPA III Скачать руководство пользователя страница 7

 

Example: There are 4 transmitters connected to the controller with a consuption of 60 mA each. The controller has a consuption of 300mA. 
The remaining 7,46 A (I=8000-300-4x60) are used to supply the visual and acoustic alarms. 

 
Information on the constuption of each transmitters and components of the visual and acoustic alarms is given in the 
respective manuals. 
 

Warning: never connect the supply voltage 24V and 230V simultaneously 

7.

 

Output relay 

Each relay can by default be configured to activate on any number and any combination of events:  

Transmitter:

 4 levels of gas leek alarms, PEL, STEL, transmitters malfunction 

Controller:

 2 levels of temperature, flooding, controller malfunction, 2 levels of exceeded temperature, flooding indication 

Relays can after activations be configured for the following output functions: normally closed, normally open, cycling of 
open/close, automatic deativation of deactivatable outputs after a certain time or after pressing a button. 
 
Specific configurations of the relays are given in the configuration protocol provided to the controller 

8.

 

Regulating the supply voltage 

 

Pomocí trimru můžeme regulovat výstupní napětí zdroje v rozsahu 22-26V. 
V případě že jsou snímače připojeny na velkou vzdálenost, může být pro správnou funkci nutné zvýšit 
napájecí napětí. 

 

Controls 

The control panel is equipped with a segmented LCD display and can be controlled using the LEFT, RIGHT and ENTER buttons. 
In Basic mode the controller displays the concentration and the states of the configured channels. Digital channels 
(transmitters connected via RS485) are numbered 1 to 32, and analog channels (connected via current loop) are in the range 
of  41 to 48. The controller sequentially switches between the configured channels (basic interval 3s).  For a longer display of a 
specific channel, briefly press ENTER (the channel remains displayed for 30s). The ENTER button also serves as a confirmation 
key for switching-off of the off-switchable outputs of the controller.  The respective output remains in the defaul state for as 
long as there is no fading of the event that triggered it (concentration drop, disappearance of the error code). 

1.

 

Panel 

 

  LCD display 

 

Indication of proper 
operation of the 
controller 

 

Gas leek 

 

LEFT button (move through 
menus, switch between 
transmitters) 

 

RIGHT button (move 
through menus, switch 
between transmitter) 

 

ENTER button 
(unblocking of the 
acoustic alarms and 
thelatch function, 
confirm) 

 

 

 

 

Содержание UPA III

Страница 1: ...ny form without the prior permission of DEGA CZ s r o is prohibited DEGA CZ s r o reserves the right to alter the specifications of the hardware and software described in this manual at any time and without prior notice DEGA CZ s r o bears no liable for any damage resulting from use of this device ...

Страница 2: ... past alarms 9 9 Automatic adjustment of the 0 point 9 10 Menu 9 History Menu HIST 10 Information menu INFO 10 Configuration menu CONF 10 Controller testing menu TEST 11 Service Menu SERV 11 Maintenance 12 1 Operation Maintenance 12 2 Replacement of the battery 12 Attachments 13 1 Table of error codes 13 General warranty terms and conditions 14 For your safety Beware of static electricity Electron...

Страница 3: ... 25 mm max 100 m Cable for connecting signalization a pushbutton cable 2 x 1mm Output USB for PC configuration RS485 protocol DEGA or MODBUS on request for the host system PLC PC 10x switching relays 250 V 10 A 2x outupt for visual and acoustic alarms max load see chapter Assembling and connecting the wiring paragraph 6 Communication speed of RS485 9 6 kB Functional safety EN61508 SIL 1 Dimensions...

Страница 4: ...e suppy voltage 22 26V Terminal block relay RE8 RE10 Fuse T400mA Auxiliary input output 24V DC Power supply terminal block 230VAC Temperature sensor terminal block Acoustic alarm lay key terminal block Flooding sensor terminal block Acoustic alarm terminal block Bus temrinal block 1 for digital transmitters Bus temrinal block 0 for digital transmitters RS485 for the host system Analog inputs Optic...

Страница 5: ...e cover of the case and lock the controller by using the handle 2 Connecting a transmitter via current loop Connect one transmitter on each channel of the controller 3 Connecting a transmitter via RS485 It is possible to connect up to 16 transmitters on each controller input depending on their electrical distance from the controller Wiring installation for RS485 Wiring must be done using bus topol...

Страница 6: ... the supply voltage and the maximum current load Supply voltage 230V AC The highest current load of the controller is 1 4A This current serves to power the connected transmitters and the visual and acoustic alarms which are connected to the terminal blocks LIGHT_SIG and SOUND_SIG Example There are 4 transmitters connected to the controller with a consuption of 60 mA each The remaining 1 16 A I 140...

Страница 7: ...imru můžeme regulovat výstupní napětí zdroje v rozsahu 22 26V V případě že jsou snímače připojeny na velkou vzdálenost může být pro správnou funkci nutné zvýšit napájecí napětí Controls The control panel is equipped with a segmented LCD display and can be controlled using the LEFT RIGHT and ENTER buttons In Basic mode the controller displays the concentration and the states of the configured chann...

Страница 8: ...cation or an evnetual sensor malfunction If the displayed channel is digital 1 to 32 the adress of the connected sensor is also displayed Connected analog transmitters have a range of 41 to 48 The controller sequentially switches the configured channels in a 3s interval If we want to select a transmitter manually we can do so with the buttons LEFT and RIGHT The status of the sensor bundled with an...

Страница 9: ...larm occurred the icon is displayed To view these alarms enter the menu HIST HILA where the date and time since the highest measured alarm since reseting HIST _RST is displayed for each transmitter After viewing the history it s possible to reset the counter throught HIST _RST and the icon disappears 9 Automatic adjustment of the 0 point The connected digital transmitters have an inner diagnostic ...

Страница 10: ...n to return the the history menu Note In case of equipping a larger quantity of transmitters the loading of the history may take a few seconds Information menu INFO NCAL Displays the date of the next transmitter calibration LCAL Displays the date of the calibration TEMP Displays the temperature of the DEGA Tc II sensor ADDR Displays the controller address on the RS485 HOST bus EXIT Returns to a hi...

Страница 11: ...nged with LEFT and RIGHT and using ENTER will confirm the selection In the final part of this whole process select either YES for saving the values into the transmitters or no for finishing the calibration without saving the values Controller testing menu TEST RELE Setting the relay output TRAN Simulation of the measured values _RST Controller restart EXIT Returns to a higher menu level The entry ...

Страница 12: ...required accuracy and the occurrance of disturbing gases in the atmoshpere Also carry out a functional control 1 x every three months checking the function of the entire detection system using a test gas which does not exceed the range of the sensor We recommend using gas intended for laboratory use For the functional control do not use means for testing fire alarm detectors Perform calibration on...

Страница 13: ... error contact the manufacturer X SEN MISM The set sensor ID does not match with the connected sensor Checking the configuration of the sensor required X ELFAILED EL sensor test error Sensor error only informative subsides by itself X X HEATING Transmitter is in preheating mode Wait a few minutes the transmitter will automatically enter measurement mode X EE25 ERR Error reading the internal FLASH ...

Страница 14: ...ct shall be replaced 616 paragraph 4 of the Commercial Code 6 The buyer who exercises the right of warranty repair is not entitled to the return of the parts that have been replaced 7 The warranty period can be extended for up to 48 months and its validity can be extended beyond the standard length on the basis of the conclusion of an individual warranty contract Further information may be obtaine...

Отзывы: