DEGA UPA III Скачать руководство пользователя страница 10

 

10 

History Menu HIST 

HI1 

Displays the alarm history for the last hour 

HI8 

Displays the alarm history for the last 8 hours 

HI12  Displays the alarm history for the last 12 hours 
HI24  Displays the alarm history for the last 24 hours 
HI2D  Displays the alarm history for the last 2 days 
HI7D  Displays the alarm history for the last week 
HIAL  Displays the alarm history for the entire memory (cca 34 days) 
HILA  Displays the alarm history since the last reset of the entry _RST 
_RST  Resets the time from which „HILA“ starts counting 
EXIT 

Returns to a higher menu level 

 
This menu displays the highest measured concentrations in a selected time interval for each channel. There is a total of 8 
intervals: - the last 1h (HI1H), 8h (HI8H), 12h (HI12H), 24h (HI24), 2 days (HI2D), 7 days, the entire memory (cca 34 days) and 
the interval since the last reset of „_RST“. Selecting an entry will perform a custom search in the memory for the selected 
channel. If during the whole interval the concentration hasn't changed and remained on the minimal value, „9999“ will be 
displayed instead of the date and time. Switch between the channel by using the arrows and use ENTER to return back to 
selecting a time interval. 
The entry _RST serves for setting the time interval for the user alarm. If since the last change of the entry _RST an alarm 
occurred at one of the transmitters, the basic status of the controller displays the segment „H“. At the entry, the date and time 
since evaluation of „HILA“ is displayed. Pressing ENTER on this entry sets the interval to the current date and time a the 
segment H disappears from the basic status. Press ENTER again to return the the history menu. 
  

Note.: In case of equipping a larger quantity of transmitters, the loading of the history may take a few seconds.

 

Information menu INFO 

NCAL  Displays the date of the next transmitter calibration 
LCAL 

Displays the date of the calibration 

TEMP  Displays the temperature of the DEGA Tc II sensor 
ADDR  Displays the controller address on the RS485 HOST bus 
EXIT 

Returns to a higher menu level 

 
For entries „LCAL“ and „NCAL“ use the arrows to switch between individual transmitters. Moving to „NCAL“displays the date 
and time of the next calibration for the selected sensor, which is connected via RS485. In addition, the main display shows the 
amount of hours remaining before the next calibration. In the same way, the entry LCAL shows the date and time of the last 
calibration for the selected channel. The main display again shows the amount of hours passed since the last calibration. This 
is a simple amount of hours, not the amount of hours, in which the sensor has been in operation. 
The entry TEMP displays the current temperature from the temperature sensor, if it'configured and connected to the 
controller. 
The entry ADDR displays the controller address on the RS485HOST bus. 

Configuration menu CONF 

To enter the menu, type in the password 0004. Use the arrows to change the value and use ENTER to move from right to left. 
Pressing enter in the order of units enters the menu. Typing in a wrong password will return us to the measurement mode. 
 
TMP1  Setting the critical temperature level 1 
TMP2  Setting the critical temperature level 2 
ALM1  Setting the 1. level of gas leek alarm 
ALM2  Setting the 2. level of gas leek alarm 
ALM3  Setting the 3. level of gas leek alarm 
ALM4  Setting the 4. level of gas leek alarm 
CALI 

Calibration of the digital transmitters 

EXIT 

Returns to a higher menu level 

 
 
 
 

Содержание UPA III

Страница 1: ...ny form without the prior permission of DEGA CZ s r o is prohibited DEGA CZ s r o reserves the right to alter the specifications of the hardware and software described in this manual at any time and without prior notice DEGA CZ s r o bears no liable for any damage resulting from use of this device ...

Страница 2: ... past alarms 9 9 Automatic adjustment of the 0 point 9 10 Menu 9 History Menu HIST 10 Information menu INFO 10 Configuration menu CONF 10 Controller testing menu TEST 11 Service Menu SERV 11 Maintenance 12 1 Operation Maintenance 12 2 Replacement of the battery 12 Attachments 13 1 Table of error codes 13 General warranty terms and conditions 14 For your safety Beware of static electricity Electron...

Страница 3: ... 25 mm max 100 m Cable for connecting signalization a pushbutton cable 2 x 1mm Output USB for PC configuration RS485 protocol DEGA or MODBUS on request for the host system PLC PC 10x switching relays 250 V 10 A 2x outupt for visual and acoustic alarms max load see chapter Assembling and connecting the wiring paragraph 6 Communication speed of RS485 9 6 kB Functional safety EN61508 SIL 1 Dimensions...

Страница 4: ...e suppy voltage 22 26V Terminal block relay RE8 RE10 Fuse T400mA Auxiliary input output 24V DC Power supply terminal block 230VAC Temperature sensor terminal block Acoustic alarm lay key terminal block Flooding sensor terminal block Acoustic alarm terminal block Bus temrinal block 1 for digital transmitters Bus temrinal block 0 for digital transmitters RS485 for the host system Analog inputs Optic...

Страница 5: ...e cover of the case and lock the controller by using the handle 2 Connecting a transmitter via current loop Connect one transmitter on each channel of the controller 3 Connecting a transmitter via RS485 It is possible to connect up to 16 transmitters on each controller input depending on their electrical distance from the controller Wiring installation for RS485 Wiring must be done using bus topol...

Страница 6: ... the supply voltage and the maximum current load Supply voltage 230V AC The highest current load of the controller is 1 4A This current serves to power the connected transmitters and the visual and acoustic alarms which are connected to the terminal blocks LIGHT_SIG and SOUND_SIG Example There are 4 transmitters connected to the controller with a consuption of 60 mA each The remaining 1 16 A I 140...

Страница 7: ...imru můžeme regulovat výstupní napětí zdroje v rozsahu 22 26V V případě že jsou snímače připojeny na velkou vzdálenost může být pro správnou funkci nutné zvýšit napájecí napětí Controls The control panel is equipped with a segmented LCD display and can be controlled using the LEFT RIGHT and ENTER buttons In Basic mode the controller displays the concentration and the states of the configured chann...

Страница 8: ...cation or an evnetual sensor malfunction If the displayed channel is digital 1 to 32 the adress of the connected sensor is also displayed Connected analog transmitters have a range of 41 to 48 The controller sequentially switches the configured channels in a 3s interval If we want to select a transmitter manually we can do so with the buttons LEFT and RIGHT The status of the sensor bundled with an...

Страница 9: ...larm occurred the icon is displayed To view these alarms enter the menu HIST HILA where the date and time since the highest measured alarm since reseting HIST _RST is displayed for each transmitter After viewing the history it s possible to reset the counter throught HIST _RST and the icon disappears 9 Automatic adjustment of the 0 point The connected digital transmitters have an inner diagnostic ...

Страница 10: ...n to return the the history menu Note In case of equipping a larger quantity of transmitters the loading of the history may take a few seconds Information menu INFO NCAL Displays the date of the next transmitter calibration LCAL Displays the date of the calibration TEMP Displays the temperature of the DEGA Tc II sensor ADDR Displays the controller address on the RS485 HOST bus EXIT Returns to a hi...

Страница 11: ...nged with LEFT and RIGHT and using ENTER will confirm the selection In the final part of this whole process select either YES for saving the values into the transmitters or no for finishing the calibration without saving the values Controller testing menu TEST RELE Setting the relay output TRAN Simulation of the measured values _RST Controller restart EXIT Returns to a higher menu level The entry ...

Страница 12: ...required accuracy and the occurrance of disturbing gases in the atmoshpere Also carry out a functional control 1 x every three months checking the function of the entire detection system using a test gas which does not exceed the range of the sensor We recommend using gas intended for laboratory use For the functional control do not use means for testing fire alarm detectors Perform calibration on...

Страница 13: ... error contact the manufacturer X SEN MISM The set sensor ID does not match with the connected sensor Checking the configuration of the sensor required X ELFAILED EL sensor test error Sensor error only informative subsides by itself X X HEATING Transmitter is in preheating mode Wait a few minutes the transmitter will automatically enter measurement mode X EE25 ERR Error reading the internal FLASH ...

Страница 14: ...ct shall be replaced 616 paragraph 4 of the Commercial Code 6 The buyer who exercises the right of warranty repair is not entitled to the return of the parts that have been replaced 7 The warranty period can be extended for up to 48 months and its validity can be extended beyond the standard length on the basis of the conclusion of an individual warranty contract Further information may be obtaine...

Отзывы: