TEX-BAR-MAN-15V05 (0903)
Copyright © 2015 Defi ne Instruments
25
16 Bit Unsigned
Address
Function
40001
Alarm status (SP1=Bit 0,
SP2=Bit 1, SP3=Bit 2, SP4=Bit 3)
40065–
40068
Hysteresis (SP1=40065, SP2=
40066, SP3=40067, SP4=40068)
40071–
40074
Make delay (SP1=40071, SP2=
40072, SP3=40073, SP4=40074)
32 Bit Signed (2 x 16 Bit)
LSW
MSW
Function
40513
40514
Process display
40525
40526
Peak
40527
40528
Valley
40535
–541
40536
–
542
Setpoint 1
–
4
(SP1=40535, SP2=40537,
SP3=40539, SP4=40541)
40587
40588
D/A scale low value
40591
40592
D/A scale high value
Modbus (RTU) Registers
Register addresses are displayed in the Modicon™ 5-digit addressing format. I.e.
Register 65=40065 (subtract 1 for direct addressing).
A.3 - Ranger A mode
Ranger A is a continuous output, used to drive remote displays and other instru-
ments in the Rinstrum™ range. (Ranger is a trade name belonging to Rinstrum Pty
Ltd.) Ranger A output strings are constructed as shown:
<Start> <Sign> <Output Value> <Status> <End>
Start -
STX character (ASCII 02)
Sign -
Output value sign (space for + and dash for -)
Output Value -
Seven character ASCII string containing the current output value and
decimal point. (If there is no decimal point, then the fi rst character is a space.
Leading zero blanking applies.)
Status -
Single character output value status. '
U
'=Under, '
O
'=Over, '
E
'=Error.
End -
ETX character (ASCII 03)