Define Instruments TEX-BAR Скачать руководство пользователя страница 1

TEX-BAR-MAN-15V05 (0903) 

Copyright © 2015 Defi ne Instruments

1

The TEX-BAR process controller off ers 

a 5-digit numeric display as well as  a 

0-100% front panel bar graph, for in-

stant, visualisation of your selected pro-

cess variable.

This versatile unit accepts both current 

(0/4–20mA) and voltage (0–2/10V) 

inputs, allowing easy interface with 

a wide range of PLC and monitoring 

systems.

TEX-BAR

4-20mA/0-10V Bar Graph

Order Codes

TEX

BAR

Process cont Bar graph

HV

LV

85–265V AC / 95–370V DC

15–48V AC / 10–72V DC

Options

-R2

-R4

2 x relay outputs

4 x relay outputs

-A

1 x mA/V analog output

-S2R

1 x RS232 (RJ11 terminal)

-S4S

1 x RS485 (screw terminal)

Contents

1 -  Specifi cations 

 .............................. 2

2 -  Front Panel & Display 

 ................. 3

3 -  Wiring 

 .......................................... 5

4 -  Dimensions & Installation 

 .......... 8

5 -  Input Header Adjustment 

 ........ 10

6 -  Input Setup & Calibration 

 ........ 12

7 -  Setpoint Setup

 ........................... 19

8 -  Setpoint Open Access

 ................ 22

9 -  Reset PIN Numbers /

View Firmware Vsn 

 ................... 22

A - Appendix A - Serial Modes

 ........ 23

Содержание TEX-BAR

Страница 1: ...LC and monitoring systems TEX BAR 4 20mA 0 10V Bar Graph Order Codes TEX BAR Processcontroller Bargraph HV LV 85 265V AC 95 370V DC 15 48V AC 10 72V DC Options R2 R4 2 x relay outputs 4 x relay output...

Страница 2: ...10V Comm Port Number of comm ports None or 1 Comm port options S2R Isolated RS232 RJ terminal or S4S Isolated RS485 screw terminal Programming Buttons Up Down Prog P buttons Factory calibrated for all...

Страница 3: ...to save your settings and advance to the next step in the setup process The Down button is used to access the Setpoint Setup menu Section 7 and the Setpoint Open Access menu Section 8 It is also used...

Страница 4: ...racters The 5 digit 7 segment display is chiefly intended for displaying numbers However when navigating the setup menus alphabetic characters will also be displayed This table is provided for your re...

Страница 5: ...e 3 6 3 1C Power Supply HV LV See 3 7 3 1D Relay Output See 3 3 3 1E Serial Port See 3 5 3 1F Analog Output See 3 4 A D B C E F 3 2 Wire the analog input See 3 1A Wire the analog input as required for...

Страница 6: ...pplied excitation 3 3 Wire the relay outputs if installed See 3 1D If your controller has relay outputs installed wire them as shown below Relays can be programmed to operate within the total span ran...

Страница 7: ...is activated Hold Holds the current display value Test Resets the meter Test Hold COM NC NC 3 7 Wire the power supply See 3 1C Wire your controller for either low or high voltage power supply as show...

Страница 8: ...IONS INSTALLATION 4 1 Case dimensions Cabling Allowance 48mm 1 89 45mm 1 77 120mm 4 72 39mm 1 54 155mm 6 10 minimum depth required behind panel 4mm 0 16 Cabling Allowance 96mm 3 78 92mm 3 62 120mm 4 7...

Страница 9: ...meter body and pro truding cabling B Remove the Mounting Clips from the meter back C Slide the Panel Gasket over the rear of the unit to the back of the Meter Faceplate D From the front of the panel i...

Страница 10: ...t posi tion of 20mA suitable for 0 20mA and 4 20mA inputs You will need to shift the input header if You are using the 0 2V or 0 10V input range or You are changing your input type or range from a pre...

Страница 11: ...Mode in software from the front panel see 6 2C G Slide the input module back into the meter case Make sure that it is sitting in the tracks on the left and right Press firmly until the input module is...

Страница 12: ...ls across the display and toggles with SKIP Press to skip to 6 3 or the button and then to ENTER input setup B _ _ _ MAINS FREQUENCY scrolls across the display Use the and buttons to select 50HZ or 60...

Страница 13: ...e uses low and high display values and is intended for a pre calibrated sensor with a known output range For example 4mA 0 and 20mA 1000 It does not require any input signals to be applied to the cont...

Страница 14: ...ed in 6 2C 0MA for 0 20mA 4MA for 4 20mA or 0V for 0 2V 0 10V F _ _ _ ENTER DISPLAY VALUE FOR HIGH MA V scrolls across the display and toggles with the current high display value Use the and buttons t...

Страница 15: ...es will stabilise measurement but it will also slow down re sponse rates A typical value is 4 C _ _ _ AVE WINDOW scrolls across the display and toggles with the currently selected averaging window val...

Страница 16: ...ect a mA or volt meter across the analog output connector see 3 4 and then continue to 6 5E If you selected Skip skip to 6 6 now E _ _ _ CAL LOW ANALOG OUTPUT scrolls across and toggles with a calibra...

Страница 17: ...n a system It applies particularly to MODBUS mode when used on an RS485 serial network The serial address of the controller must be set to match the serial address defined in the master device Refer t...

Страница 18: ...ay and toggles with SKIP Press to skip and return to the operational display or the button and then to ENTER and change your PIN number B _ _ _ ENTER NEW CAL PIN NUMBER scrolls across the display and...

Страница 19: ...PIN is entered setup is started at 7 2 If an incorrect PIN number is entered _ _ _ INCORRECT PIN NUMBER ACCESS DENIED scrolls across the display and it returns to normal operating mode You will have...

Страница 20: ...RESIS VALUE defines the separation band between setpoint activation and deacti vation and will operate as per the SETPOINT TYPE setting selected in 7 2D F _ _ _ MAKE DELAY scrolls across the display a...

Страница 21: ...ingle bar Multiple setpoints may have this option enabled Use the and buttons to select NO or YES and then press K _ _ _ EDIT SETPOINT scrolls across the display and toggles with SKIP You are now back...

Страница 22: ...he last ena bled setpoint will exit and return to the operational display 9 RESET PIN NUMBERS VIEW FIRMWARE VERSION If you have forgotten your PIN number s follow the procedure below to reset both the...

Страница 23: ...ed data which includes decimals and any text characters that may be selected to show units However it is also possible to read un formatted data by using a U in the read command There is no unformatte...

Страница 24: ...Signed Address Function 2 Process display 12 Peak 13 Valley 6 9 Setpoint 1 4 SP1 6 SP2 7 SP3 8 SP4 9 34 D A scale low value 36 D A scale high value Custom ASCII Registers Controller Response After the...

Страница 25: ...ster addresses are displayed in the Modicon 5 digit addressing format I e Register 65 40065 subtract 1 for direct addressing A 3 Ranger A mode Ranger A is a continuous output used to drive remote disp...

Страница 26: ...TEX BAR MAN 15V05 0903 Copyright 2015 Define Instruments 26...

Страница 27: ...TEX BAR MAN 15V05 0903 Copyright 2015 Define Instruments 27...

Страница 28: ...835 1550 Aus 1800 810 820 Fax 64 9 835 1250 sales defineinstruments co nz www defineinstruments co nz United States Dallas TX Ph 214 926 4950 sales defineinstruments com www defineinstruments com Sout...

Отзывы: