7
Beachten Sie bitte die nachfolgenden Anschlussdaten:
Gerätetyp
Netzcode
1)
Strom
Leistung
Min. Leitungsquerschnitt
Max. Vorsicherung “F1”
in A
in kW
pro Leiter in mm2
in A, flink
12 (400 V 3~)
5.5
4.0
1.5
10
13 (220 V 3~)
9.5
3.5
2.5
16
ST 5-../IT 5-..
14 (415 V 3~)
6.0
4.0
1.5
10
15 (240 V 1N~)
17.0
4.0
4.0
20
16 (230 V 1N~)
16.5
4.0
4.0
20
17 (200 V 3~)
8.2
3.0
1.5
10
12 (400 V 3~)
11.0
7.5
2.5
16
13 (220 V 3~)
18.0
7.0
4.0
20
ST 10-../IT 10-..
14 (415 V 3~)
11.5
8.0
2.5
16
15 (240 V 1N~)
34.0
8.0
10.0
40
16 (230 V 1N~)
33.0
7.5
10.0
40
17 (200 V 3~)
16.4
6.0
4.0
20
12 (400 V 3~)
21.5
15.0
6.0
25
13 (220 V 3~)
35.5
13.5
10.0
40
ST 20-../IT 20-..
14 (415 V 3~)
22.5
16.0
6.0
25
15 (240 V 1N~)
–
–
–
–
16 (230 V 1N~)
–
–
–
–
17 (200 V 3~)
32.5
11.0
10.0
40
12 (400 V 3~)
32.5
22.5
10.0
40
13 (220 V 3~)
53.5
20.0
16.0
60
ST 30-../IT 30-..
14 (415 V 3~)
33.5
24.0
10.0
40
15 (240 V 1~)
–
–
–
–
16 (230 V 1~)
–
–
–
–
17 (200 V 3~)
48.5
17.0
16.0
60
1)
Sonderspannungen auf Anfrage
Hinweis: Die Dampf-Luftbefeuchter ST 40-.. bis ST 90-.. bzw. IT 40-.. bis IT 90-..
sind Mehrfachgeräte (2er- und 3er-Module), aufgebaut aus den vorgängig auf-
geführten Einzelgeräten (Beispiel: das Gerät ST 50-.. besteht aus den Einzelmodu-
len ST 20-.. und ST 30-..). Für die Mehrfachgeräte sind deshalb die Anschlussdaten
der jeweiligen Einzelgeräte zu beachten.
Wichtige Hinweise:
- Zugentlastung: Befestigen Sie das Anschlusskabel in jedem Fall mit dem dafür
vorgesehenen Klemmhalter am Gerät.
- In der Versorgungsleitung ist ein
Serviceschalter “Q”
(minimale Kontaktöffnung
3 mm) zu installieren. Er sollte in der Nähe des Gerätes installiert werden, damit
die Stromzufuhr jederzeit unterbrochen werden kann. Der Serviceschalter ist
nicht im Lieferumfang enthalten.