Please observe the following connection data:
Unit
Mains code
1)
Current
Power
Min. conductor cross-sect.
Max. prefusing “F1”
in A
in kW
per conductor in mm2
in A, quick-acting
12 (400 V 3~)
5.5
4.0
1.5
10
13 (220 V 3~)
9.5
3.5
2.5
16
ST 5-../IT 5-..
14 (415 V 3~)
6.0
4.0
1.5
10
15 (240 V 1N~)
17.0
4.0
4.0
20
16 (230 V 1N~)
16.5
4.0
4.0
20
17 (200 V 3~)
8.2
3.0
1.5
10
12 (400 V 3~)
11.0
7.5
2.5
16
13 (220 V 3~)
18.0
7.0
4.0
20
ST 10-../IT 10-..
14 (415 V 3~)
11.5
8.0
2.5
16
15 (240 V 1N~)
34.0
8.0
10.0
40
16 (230 V 1N~)
33.0
7.5
10.0
40
17 (200 V 3~)
16.4
6.0
4.0
20
12 (400 V 3~)
21.5
15.0
6.0
25
13 (220 V 3~)
35.5
13.5
10.0
40
ST 20-../IT 20-..
14 (415 V 3~)
22.5
16.0
6.0
25
15 (240 V 1N~)
–
–
–
–
16 (230 V 1N~)
–
–
–
–
17 (200 V 3~)
32.5
11.0
10.0
40
12 (400 V 3~)
32.5
22.5
10.0
40
13 (220 V 3~)
53.5
20.0
16.0
60
ST 30-../IT 30-..
14 (415 V 3~)
33.5
24.0
10.0
40
15 (240 V 1~)
–
–
–
–
16 (230 V 1~)
–
–
–
–
17 (200 V 3~)
48.5
17.0
16.0
60
1)
Special voltages available on demand
Note: The ST 40-.. to ST 90-.. and IT 40-.. to IT 90-.. steam humidifiers are multiple
units (2 and 3 modules) based on the previously described single units (e.g. the unit
ST 50-.. consists of the single module ST 20-.. and ST 30-..). The connection data
for the relevant single units should therefore be observed for the multiple units.
Important notes:
- Tension relief: the connecting cable should be secured in each case with the
clamping holder on the unit provided for this purpose.
- A
service switch “Q”
(minimum contact opening 3 mm) should be fitted in the
supply line. It should be close to the unit so that the power supply can be
interrupted at any time. The service switch is not included in the delivery.