24
1.6
Adjustments
Important notes
- Warning! Disconnect the steam humidifier from the mains supply (power and
control unit) before starting the adjustments.
- Alteration of settings not described below is not permitted and may lead to injury
to persons and material damage.
All adjusting elements are situated on the control p.c.b.:
- DIP switch “SW1”:
General adjustments
- Rotary switch “SW2”:
Control signal range
- Rotary switch “SW3”:
Maintenance interval
- Rotary switch “SW4”:
Flushing intervals
General settings (“SW1”)
Switch
Standard setting
Description
1
OFF
Stand-by heating ON/OFF
With stand-by heating switched on, the water in the steam boiler is kept at a specific
temperature if steam production stops, so that steam can be produced again immediately if
required.
2
OFF
Cleaning cycle ON/OFF
With the cleaning cycle switched on, flushing is performed for 10 seconds every 168
operating hours.
Important!
During the cleaning cycle no steam can be produced for approx. 10 minutes
owing to cooling.
3
OFF
Pulse/pause package control ON/OFF
If this position is activated (ON) the control performance is optimized. If deactivated (OFF)
it is regulated normally (maintenance of flicker regulations)
4
OFF
Spare
5
OFF
Automatic flushing of the steam cylinder ON/OFF
If this setting is enabled (ON) the steam cylinder is automatically flushed after 72 hours
(hygiene)
6 - 8
OFF
Spare