31
Veuillez observer les données de raccordement suivantes:
Type d’appareil
Code secteur
1)
Courant
Puissance
Section min. par fil
Fusible préliminaire “F1”
en A
en kW
conducteur en mm2
en A, rapide
12 (400 V 3~)
5.5
4.0
1.5
10
13 (220 V 3~)
9.5
3.5
2.5
16
ST 5-../IT 5-..
14 (415 V 3~)
6.0
4.0
1.5
10
15 (240 V 1N~)
17.0
4.0
4.0
20
16 (230 V 1N~)
16.5
4.0
4.0
20
17 (200 V 3~)
8.2
3.0
1.5
10
12 (400 V 3~)
11.0
7.5
2.5
16
13 (220 V 3~)
18.0
7.0
4.0
20
ST 10-../IT 10-..
14 (415 V 3~)
11.5
8.0
2.5
16
15 (240 V 1N~)
34.0
8.0
10.0
40
16 (230 V 1N~)
33.0
7.5
10.0
40
17 (200 V 3~)
16.4
6.0
4.0
20
12 (400 V 3~)
21.5
15.0
6.0
25
13 (220 V 3~)
35.5
13.5
10.0
40
ST 20-../IT 20-..
14 (415 V 3~)
22.5
16.0
6.0
25
15 (240 V 1N~)
–
–
–
–
16 (230 V 1N~)
–
–
–
–
17 (200 V 3~)
32.5
11.0
10.0
40
12 (400 V 3~)
32.5
22.5
10.0
40
13 (220 V 3~)
53.5
20.0
16.0
60
ST 30-../IT 30-..
14 (415 V 3~)
33.5
24.0
10.0
40
15 (240 V 1~)
–
–
–
–
16 (230 V 1~)
–
–
–
–
17 (200 V 3~)
48.5
17.0
16.0
60
1)
Autres voltages sur demande
Indication: les humidificateurs à vapeur ST 40-.. à ST 90-.., resp. IT 40-.. à IT 90-
.. sont des appareils multiples (modules doubles et triples) conçus à partir du modèle
unitaire précédent (exemple: le modèle ST 50-.. se compose des modules unitaires
ST 20-.. et ST 30-..). Les valeurs de branchement de chaque appareil doivent donc
être cumulées en cas de version multiple.
Conseils importants
:
- Décharge de traction: toujours fixer le câble de raccordement avec la bride de
câble prévue à cet effet dans l’appareil.
- Un
interrupteur de service “Q”
(ouverture minimale des contact de 3 mm) doit
être installé dans la ligne d’alimentation électrique. Celui-ci devrait se trouver
à proximité de l’appareil afin de pouvoir interrompre l’alimentation électrique
à tout moment. L’interrupteur de service n’est pas compris dans la livraison.