34
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006
11.1.4 PLUG “G” 5 WAY
PIN No
DESCRIPTION
CABLE SIZE
NOTES
39
CT Secondary for L1
2.5mm² (13 AWG)
Connect to secondary of L1 monitoring
CT
40
CT Secondary for L2
2.5mm² (13 AWG)
Connect to secondary of L2 monitoring
CT
41
CT Secondary for L3
2.5mm² (13 AWG)
Connect to secondary of L3 monitoring
CT
42
CT secondary common
2.5mm² (13 AWG)
Connect to secondary of all monitoring
CT’s
43 Not
connected
-
11.1.5 PLUG “H” 4 WAY
PIN No
DESCRIPTION
CABLE SIZE
NOTES
44
Oil Pressure Input
0.5mm² (20 AWG)
Connect to Oil pressure sender
45 Coolant
Temperature
Input
0.5mm² (20 AWG)
Connect to Coolant Temperature sender
46 Not
connected
-
47
Sender Common Return
0.5mm² (20 AWG)
Return feed for senders*.
NOTE*:- If using single terminal senders refer to connection diagram. If using earth return
type senders connect return terminals to pin 47 and also connect pin 47 to earth. This is detailed
in the Appendix section entitled “Sender wiring recommendations” elsewhere in this manual.