2. The unit is equipped with a lift pump which can pump up to 700 mm. However, when the pump is off,
the water remaining in the pipe will be drained out and risks overflowing the condensate collector box,
causing a water leak.
3. When condensate is discharged from several units using a common discharge pipe, this common
discharge pipe must be installed approx. 100 mm below the condensate discharge outlet of each
indoor unit, as shown in the diagram below.