Measurement
type
Unit
GSHP 5
MR-E
GSHP 5
TR-E
GSHP 9
MR-E
GSHP 9
TR-E
GSHP
12 MR-E
GSHP
12 TR-E
GSHP
15 TR-E
GSHP
19 TR
GSHP
27 TR
Coefficient of
performance
(COP)
4.25
4.25
4.37
4.37
4.20
4.20
4.27
4.12
3.90
Absorbed electri
cal power
kWe
1.65
1.65
2.86
2.86
3.80
3.80
5.02
6.54
8.83
Heat output
kW
7.01
7.01
12.51
12.51
15.94
15.94
21.44
26.95
34.40
Tab.10 Common specifications
Measurement
type
Unit
GSHP 5
MR-E
GSHP 5
TR-E
GSHP 9
MR-E
GSHP 9
TR-E
GSHP
12 MR-E
GSHP
12 TR-E
GSHP
15 TR-E
GSHP
19 TR
GSHP
27 TR
Power supply V
(~50 Hz)
230
single
phase
400
three-
phase
230
single
phase
400
three-
phase
230
single
phase
400
three-
phase
400
three-
phase
400
three-
phase
400
three-
phase
Start-up am
perage
A
<30
<30
<30
<30
<30
<30
<30
<30
<30
Maximal am
perage
A
12.8
4.8
22.8
7.4
27.9
9.7
13
15.3
21.6
Sound output dB(A)
49
49
53
53
52
52
51
53
50
Refrigerant
fluid R410A
kg
1.50
1.50
1.70
1.70
1.80
1.80
2.50
2.54
3.18
Refrigerant
fluid R410A
tCO
2
e
(1)
3.13
3.13
3.55
3.55
3.76
3.76
5.22
5.30
6.64
Weight
kg
127
127
143
143
143
143
161
147.5
161.5
(1) Quantity of refrigerant fluid is calculated in tonnes of CO
2
equivalent.
Note
The values in tonnes of CO
2
equivalent are calculated using the
following formula: quantity (in kg) of refrigerant fluid x GWP /
1000.
The Global-Warming Potential (GWP) of R410A gas is 2088.
Note
R410A refrigerant fluid is contained in equipment that has been
hermetically sealed.
Other technical parameters
Tab.11 Technical parameters for heat pump space heaters (parameters declared for medium-temperature application)
GSHP
GSHP 5 MR-
E
- GSHP 5
TR-E
GSHP 9 MR-
E – GSHP 9
TR-E
GSHP 12
MR-E –
GSHP 12
TR-E
GSHP 15
TR-E
Air-to-water heat pump
No
No
No
No
Water-to-water heat pump
Yes
Yes
Yes
Yes
Brine-to-water heat pump
No
No
No
No
Low-temperature heat pump
No
No
No
No
Equipped with a supplementary heater
Yes
Yes
Yes
Yes
Heat pump combination heater
No
No
No
No
Rated heat output under average condi
tions
(1)
Prated
kW
7
12
15
21
3 Technical specifications
16
GSHP
7636860 - v04 - 18012017