Installer level - #NETWORK Menu
(1)
Parameter
Adjustment range Description
Factory setting Customer
setting
CASCADE
ON
/
NO
ON
: System in cascade
NO
VM NETWORK
Specific menu: Enlist VMs in cascade
mode (See following chapter: "Connect
VMs only in cascade")
MASTER CONTROLER
(2)
ON
/
NO
Configure this control system as master
on the bus
ON
SYSTEM NETWORK
(3)
Specific menu: Enlist generators or
VMs in cascade mode (See following
chapter: "Connecting appliances in
cascade")
FUNCT
(3)
TRADITIONAL
Operation in cascade: Successive
triggering of the various boilers in the
cascade according to requirements
TRADITIONAL
PARALLEL
Functioning in parallel cascade: If the
outside temperature is lower than the
value
PARALLEL.CASC
, all of the
boilers are started up at the same time
PARALLEL.CASC
(4)
-10 to 20 °C
Outside temperature triggering all
stages in parallel mode
10 °C
TIMER GENE P.CASC
(2)
0 to 30 min
Minimum duration of post-operation of
the generator pump
0 mn
INTER STAGE TIMER
(2)
1 to 30 min
Time delay for starting up or shutting
down generators.
4 mn
SLAVE NUMBER
(5)
2 to 10
Set the network address of the
secondary generator
2
(1) The menu is displayed only if the
INSTALLATION
parameter is set to
EXTENDED
UE}
(2) The parameter is only displayed if
CASCADE
is set to
ON
(3) The parameter is only displayed if
MASTER CONTROLER
is set to
ON
(4) The parameter is only displayed if
FUNCT
is set to
PARALLEL
(5) The parameter is only displayed if
MASTER CONTROLER
is set to
OFF
User level - #SETTING Menu
Parameter Adjustment range Description
Factory setting Customer setting
PERMUT
(1)
AUTO
/ 1 ... 10
This parameter is used to set the master boiler.
4
AUTO
: The master boiler switches automatically
every 7 days
4
1 ... 10: The master boiler is always the one
defined by this value
AUTO
(1) The parameter is only displayed if
CASCADE
is on
ON
and
MASTER CONTROLER
on
ON
n
Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/or
VM iSystem as slaves. Proceed as follows:
1. Set parameter
CASCADE
to
ON
.
5. Commissioning
Diematic iSystem For C 330 / C 630 ECO
61