Code Faults
Cause
of the
fault
Description
Checking / solution
L11
DEF.DT.RET.ECH
PCU
Difference between the return
temperature and the exchanger
temperature too big
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
Bad connection
4
Check that the sensor has been correctly fitted
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
4
Check that the heating pump is operating
correctly
L12
STB OPEN
PCU
4
Maximum boiler temperature
exceeded (STB thermostat
maximum)
4
Air differential pressure switch
has been triggered
Bad connection
4
Check the wiring between the PCU PCB and the
STB
4
Check that the SU PCB is correctly in place
4
Check the electrical continuity of the STB
4
Check whether the STB has been correctly fitted
STB failure
4
Replace the STB if necessary
4
Check that the sensor has been correctly fitted
4
Check for correct operation
No water circulation
4
Remove the air from the installation
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
4
Check that the heating pump is operating
correctly
Air pressure switch is triggered
4
Check that the air inlet and flue gas discharge
flues are not blocked
4
Check that condensate has been removed and
the cleanliness of the siphon
4
Check the cleanliness of the heat exchanger
(Flue gas dimensions)