Installer level - #SECONDARY INSTAL.P Menu
Parameter
Adjustment range
Description
Factory
setting
Customer
setting
BUILD.INERTIA
(1)
0 (10 hours) to 10
(50 hours)
Characterisation of building’s inertia:
0 for a building with low thermal inertia.
3 for a building with normal thermal
inertia.
10 for a building with high thermal inertia.
Modification of the factory setting is
only useful in exceptional cases.
3 (22 hours)
CIRC.CURVE A
(2)
0 to 4
Heating curve of the circuit A
¼
1.5
ANTICIP.A
(1)
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼
NO
ROOM INFL.A
(1)
0 to 10
Influence of room sensor A
¼
3
CIRC.CURVE B
(2)
0 to 4
Heating curve of the circuit B
¼
0.7
ANTICIP.B
(1)
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼
NO
ROOM INFL.B
(1)
0 to 10
Influence of room sensor B
¼
3
CIRC.CURVE C
(2)
0 to 4
Heating curve of the circuit C
¼
0.7
ANTICIP.C
(1)
0.0 to 10.0
Activation and adjustment of the
anticipation time
¼
NO
ROOM INFL.C
(1)
0 to 10
Influence of room sensor C
¼
3
SCREED DRYING
NO, B, C, B+C
Drying the floor
¼
NO
START DRYING TEMP
(3)
20 to 50 °C
Screed drying start temperature
20 °C
STOP DRYING TEMP
(3)
20 to 50 °C
Screed drying stop temperature
20 °C
NB DAYS DRYING
(3)
0 to 99
0
NIGHT
(1)
DEC.
The lower temperature is maintained
(Night mode)
¼
DEC.
STOP
The boiler is stopped (Night mode)
¼
IN 0-10V
OFF
/
TEMPERATURE
/
POWER %
Activating the 0-10 V function
¼
OFF
(1) The parameter is only displayed if
INSTALLATION
is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
(3) The parameter is only displayed if
SCREED DRYING
is different from
OFF
(4) The parameter is only displayed if
IN 0-10V
is set to
ON
.
(5) The parameter is only displayed if
P.DHW
is set to
PUMP
(6) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
(7) The parameter is only displayed if
LEG PROTEC
is different from
OFF
5. Commissioning