Brine Generator Installation (Optional)
Plumbing Connections
Place the brine generator on a flat surface that is capable of handling the load of a fully loaded tank. A
1,000 gallon tank can hold up to 9,000 lbs. of salt. Sweep the floor prior to installation. Debris left
under a tank can permanently damage the tank. Rotate the tank to align inlet and outlet fittings that
best suit the installation. Plumb softened water to the inlet of the tank. It is recommended that an
isolation valve be installed on the water line prior to the tank to assist with maintenance. Plumb the
overflow fitting to a drain. Verify the overflow line has an adequate air gap to prevent cross
contamination of the brine generator. Plumb the outlet fitting to the OSG (Figure 5).
Note: Outlet plenum should be installed before float assembly.
Note: Use Teflon tape on threaded plumbing connections.
Brine Tank Float and Spray Ring Assembly
MIOX Corporation has adapted an off-the-shelf float valve and spray ring assembly for providing
saturated brine to the on-site generator. Kinetico® provides KCBS (Kinetico® Central Brine System)
which includes a float valve assembly with a 28” height adjustment range to allow for a broader range of
tank fill levels.