13 / 14
WWW.DDTOP.COM
any point in the range. (Enter compensation value) The setup process is as follows.
① Press and hold the '←' key to enter the configuration mode (the No. 1 menu will be displayed
first, and the up and down arrows on the left will be lit).
② Press the "↑" key to switch the menu to '9' and the LCD shows the current PV compensation
value.
③ Press the '←┘' key again, the symbol starts flashing, now press the '↑' key or '↓' to switch to
the positive or negative sign you want to set.
④ Press the "←┘" key again to complete the setting, and the highest setting parameter blinks. At
this time press "↑" or "↓" to increment or decrement the current blinking digit, press "←" to
confirm and start the next digit setting, and then set the other digits and decimal points.This menu
function setting is completed when the left up and down arrows are lit.
Method of calculating the compensation value.
Compensated value = PV actual - PV pre-output
Note: The key configuration process will not exit automatically, you need to exit the key
configuration manually. The method is to press the '↑' key or '↓' key continuously in the switch
menu state, the menu will increase or decrease, when the menu is greater than 17 or less than
1, exit the key configuration state and enter the normal output mode.
8 Precautions
8.1 The temperature of the medium must not exceed 120°C, otherwise the sensor circuit will be
damaged.
8.2 Confirm that the power supply is safe and reliable and that it is connected in accordance with
the correct positive and negative polarity.
8.3 The use of UQZ magnetic float level transmitter is not suitable for occasions with high vibration.
8.4 Media viscosity ≥ 10-4 (m2 / s), not suitable for use of UQZ magnetic float level transmitter.
8.5 UQZ magnetic float level transmitter should not work in a strong magnetic field environment.
8.6 Tighten the power cover of the display after debugging to prevent water and moisture in the
meter.