10 / 14
WWW.DDTOP.COM
7.1.4 Parameter Configuration Method Explanation
Long press "←┘" when the "888" character in the lower left corner shows 1~17, it means the
transmitter is in the field configuration mode of menu rotation, now you can enter initialization code,
modify parameters, meter calibration or migrate by pressing the key.
The data setting process utilizes.
The "←┘" key is used to select the digits and decimal points to be edited and the final confirmation
of the save.
(Blinking for selected status)
The "↑" key is used to blink the number digits incrementally from 0 to 9 and to move the decimal
point to the right.
The "↓" key is used to flash the number of digits in decreasing order from 9 to 0 and to move the
decimal point to the left.
The setting process is as follows.
1. Press and hold down the key '←' to enter the data configuration interface, the lower left corner
will show '01' and the data line will show '00005'. Press the '←┘' key again, the symbol bit will
blink, indicating that the symbol bit can be modified.
2.If you press '↑' or '↓' key again, you can switch between positive and negative sign of data.
3. If you press the '←┘' key again, the first digit starts blinking when the selection of the symbol is
finished, it means the symbol bit can be modified. The numbers cycle between 0 and 9.
4. Press the '←┘' key again, the first digit is finished and you can set the second to fifth digit in the
same way as the first one.
5. After setting the fifth digit, press '←┘' key again to set the decimal point. The decimal point
starts blinking at the same time, which means you can set the decimal point, press '↑' key or '↓'
key to switch the decimal point position to the right or left circularly.
6. After the decimal point is set, press '←┘' key, the up and down arrows on the left side will light
up, which means save the setting.
7. Press the '←┘' key again to set the data again.
7.1.5 Keycode Lookup Table
When the key is used for field configuration, the two "888" display bit characters in the lower left
corner of LCD indicate the current setting menu number, which is the setting function performed by
the current key. The correspondence is as follows.
The "888" display bit in the lower left corner
shows
Set variables
0 or blank
Normal display
1
Enter operation code (00911 initialize instrument)
2
Set units
3
Set LRV
4
Set URV