background image

Unpacking

  1                                                   www.dcionline.com

C1000 Series Service & Maintenance Manual

Maintenance

Maintenance

SECTION III

Unscrew the 

fi

 lter bowl by turning counter-clockwise. Lower the 

fi

 lter bowl to access the 

fi

 lter element contained inside. The 

fi

 lter element is held in place with an O-ring and 

internal ridges located in the bowl. Replace with DCI Part Number 2006, and reassemble 
the 

fi

 lter bowl. Turn the dryer bypass valve to the ON position and check compressor for 

proper operation by turning the power switches on. 

NOTE: A “popping” relief valve indicates a clogged coalesing element OR 
the Dryer Bypass valve is closed. 

B.   Coalescing Filter Element

The coalescing 

fi

 lter element should be checked with the compressor motors running. If 

the indicator located on the top of the 

fi

 lter housing remains GREEN, the 

fi

 lter element has 

additional useful life. However, if the indicator turns RED, the element should be changed. 
To change the element, 

fi

 rst turn off the compressor motor switches. Then turn off the 

Dryer bypass valve as shown in (Fig. E). With dryer bypass valve in OFF position, press the 
TEST button on the time operated purge valve to bleed pressure off of the drying system. 
Depressurization of the drying system can be con

fi

 rmed by reading the drying system 

pressure gauge located on top of the drying chamber. 

WARNING

: DO NOT ATTEMPT TO SERVICE WITH SYSTEM PRESSURIZED.

Fig. D

Fig. E

ON

OFF

COMPRESSOR MAINTENANCE SCHEDULE

    Maintenance Item                                               Frequency                       
Intake Filter Elements 

 

Every Six Months (semi-annually)

Coalescing Filter Element 

 

Every 90 Days

Time Operated Purge Valve   

Every 60 Days

Tank Drain 

 

 

Every 90 Days

A.   Compressor Head Intake Filter Elements

Dirty intake 

fi

 lter elements reduce the amount of air the compressor can take in. This 

reduces air output and increases the load of the motors. Every six months, remove 
the intake 

fi

 lter cover as shown in (Fig. D), to check for excessive dirt or discoloration. 

Replace with DCI Part Number 2012 if needed.  The 

fi

 lters are located on the rear of each 

compressor cylinder.

MAINTENANCE

w w w.dcionline.com

8

Содержание C1103

Страница 1: ...D C1203 D C2106 D C2206 D C3210 C Series COMPRESSOR Copyright 2006 DCI All Rights Reserved D C1103 D C1203 D C2106 D C2206 D C3210 C Series COMPRESSOR Compressor Service Maintenance Manual 92311 Rev...

Страница 2: ...1 www dcionline com www dcionline com...

Страница 3: ...SERVICE REPAIR INSTRUCTIONS A Troubleshooting Chart B Electrical 1 Replacing Pressure Switch 2 Replacing Power Switch 3 Replacing Compressor Head 4 Replacing Time Operated Purge Valve C Pneumatic 1 Re...

Страница 4: ...service procedures before attempting to service this machine Our unique dryer purge system operates much differently than conventional air compressors Understanding the proper operation and design wil...

Страница 5: ...ons 1 Single 1 horsepower compressor head on 20 gal Horizontal tank See Fig A 2 Dual 1 horsepower compressor heads on 20 gal Horizontal tank See Fig B 3 Dual 1 horsepower heads on 30 gal horizontal ta...

Страница 6: ...5 C1203 3 95 1 20 34 24 29 5 230 6 7 10 C2106 7 95 2 20 34 24 29 5 115 26 8 30 C2206 7 95 2 20 34 24 29 5 230 13 4 15 C3210 11 85 3 30 46 26 36 230 21 1 30 NOTE ALL VOLTAGES ARE 5 MODEL NUMBER MAXIMUM...

Страница 7: ...ttom of the filter bowl The compressed air also travels through the coalescing filter element which removes 99 998 of all particles down to 0 01 microns A filter change indicator located on the top of...

Страница 8: ...e compressor cycles off C The Left timer knob on the purge valve controls the duration of the purge cycles This timer is factory preset and should not be adjusted The factory setting is at the maximum...

Страница 9: ...C1000 Series Service Maintenance Manual Theory of Oporation Theory of Operation THEORY OF OPERATION While Not Running Electrical Schematic SECTION II 1 800 624 2793 7...

Страница 10: ...e element first turn off the compressor motor switches Then turn off the Dryer bypass valve as shown in Fig E With dryer bypass valve in OFF position press the TEST button on the time operated purge v...

Страница 11: ...floor Check the filter screen inside the filter strainer valve as shown in Fig G If the strainer shutoff valve is on and the screen is not clogged replace the Time Operated Purge Valve with DCI part N...

Страница 12: ...breaker Ensure that supply voltage matches equipment ratings Check for loose wiring Check contact points and adjust or replace Bleed pressure from system to ensure proper starting Ensure supply volta...

Страница 13: ...or replace intake filter element Clean Replace valve plate Air leaks compressor too small to meet demand Add ventilation and or cooling to equipment room Clean or replace solenoid valve assembly Left...

Страница 14: ...oltage indicated should agree with the machine data plate either 115 or 230 volt AC If no voltage is present check the circuit breaker Fig I Fig J ELECTRICAL If the proper voltage is present on the ou...

Страница 15: ...on up position check for voltage to the compressor motor as shown in Fig K If the proper voltage is present the power switch is good If no voltage is present at the motor replace the corresponding po...

Страница 16: ...embly 2 Turn OFF the strainer shutoff valve in Fig N 3 Remove the valve and replace with DCI Part Number 2011 for 230 volt machines OR DCI Part Number 2848 for 115 volt models 4 Return the strainer sh...

Страница 17: ...Replace the differential filter indicator by unscrewing the entire assembly counterclockwise with a 15 16 6 point box end wrench Install the new indicator in the reverse order 3 Automatic Filter Float...

Страница 18: ...er 2006 Coalescing Element 2135 Check Valve 2135 Check Valve 2014 Drying Chamber Assembly Pressure Gauge 2011 Automatic Purge Valve 230 Volt OR 2848 Automatic Puge Valve 115 Volt 2009 Strainer Shut Of...

Страница 19: ...C1000 Series Service Maintenance Manual Illustrated Parts Breakdown SECTION V Unpacking Electrical Schematic 1 800 624 2793 17...

Страница 20: ...ION V Unpacking Plumbing Schematic Left Motor Right Motor Check Valve Check Valve Aftercooling Tubing Coalescing Filter Condensate Drain Drying Chamber Flow Check Drying System Pressure Gauge Dryer By...

Страница 21: ...1 800 624 2793 19...

Страница 22: ...305 N Springbrook Road Newberg Oregon 97132 USA 503 538 8343 800 624 2793 www dcionline com...

Отзывы: