INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pumps

8

428 01 1703 01

Specifications subject to change without notice.

Replace stem caps after system is opened to

refrigerant flow.  Replace caps finger

tight and tighten

with wrench an additional 1/12 turn

3. Close electrical disconnects to energize system.
4. Set room thermostat or Observer Wall Control at

desired temperature. Be sure set point is below indoor

ambient temperature.

5. Set room thermostat to HEAT or COOL and fan control

to ON or AUTO mode, as desired. Operate unit for 15

minutes. Check system refrigerant charge.

Figure 10

Observer Communicating Wall Control

Four

Wire Connection Diagram

S1
S2

R

C

DX

DX+

Optional Remote

Room Sensor

HUM

COM

C

DX

DX+

Humidifier

Connection

Green

Yellow

White

Red

R

Green

Yellow

C

DX

DX+

Observer

Communicating

Wall Control

Communicating

Variable Speed

Furnace/Fan Coil

Two-Stage
Heat Pump

NOTE

: Wiring must conform to NEC or local codes.

NOTE

: For standard thermidistat or thermostat wiring, see

Installation Instructions for those products.

Figure 11

FVM Fan Coil Wiring With 

Two

Stage Heat Pump

Fan Coil

Indoor Control

G

O/W2

R

Y1/W2

W/W1

Y/Y2

DHUM

C

HUM

B

S1

S2

RVS Cooling

Heat/Cool

Stage 1

Heat Stage 3

Heat/Cool

Stage 2

Fan

24 VAC Hot

Dehumidify

24 VAC Comm

Humidify

RVS Heating

Outdoor

G

O

R

W1

Y/Y2

C

Y1

W2

H

O

Y1

Y2

C

W1

Two-Stage Heat Pump

Remove J2 Jumper
For Heat Staging

s

s

Humidifier

(24 VAC)

Outdoor

Sensor

Figure 12

Variable Speed Furnace with 

Two

Stage Heat Pump (Dual Fuel)

Variable Speed

Furnace

ICP Thermostat

G

W2

R

Y1

W1

Y2

C

DHUM

OD

GND

H

Y1

Y2

C

W1

Two-Stage
Heat Pump

G

W2

R

Y1

W/W1

Y/Y2

COM

HUM

L

O/B

OUTDOOR

SENSOR

O

Figure 13

Non

Communicating Indoor Unit with 

Observer Communicating Wall Control

NAXA00101DB

Green

Yellow

White

Red

OAT

Sensor

Communicating

Outdoor

W2

C

Y1

W1

C

R

 

Wall

Control

OAT

DX+

R

C

DX-

Y1

G

O

O

C

Y1

R

W2

G

DX+

R

C

DX-

Non-Communicating

Indoor

Note: This installation requires the daugh­
ter board accessory, NAXA00101DB.
Note: This installation does not allow for
communicating feature functionality.

Y2

Y2

Y/Y2

Check Charge

Two

stage equipment should be charged in high

stage

compressor operation only.

Factory charge amount and desired subcooling are shown

on unit rating plate. Charging method is shown on information

plate inside unit. To properly check or adjust charge,

conditions must be favorable for subcooling charging.

Favorable conditions exist when the outdoor temperature is

between 70

F and 100

F (21.11

C and 37.78

C), and the

indoor temperature is between 70

F and 80

F (21.11

C and

26.67

C). Follow the procedure below:

Содержание CCH9

Страница 1: ...hanced installation reliability or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manu...

Страница 2: ...d refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube...

Страница 3: ...ctions from kit for installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent damage to the unit ensure that it is located...

Страница 4: ...ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 2...

Страница 5: ...E HAZARD Failure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DA...

Страница 6: ...d Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to fol...

Страница 7: ...ment size See Observer Wall Control Installation Instructions and indoor specification sheet for available adjustments Airflow Setup with Non Communicating Furnace or Fan Coil Two stage compressor ope...

Страница 8: ...age 1 Heat Stage 3 Heat Cool Stage 2 Fan 24 VAC Hot Dehumidify 24 VAC Comm Humidify RVS Heating Outdoor G O R W1 Y Y2 C Y1 W2 H O Y1 Y2 C W1 Two Stage Heat Pump Remove J2 Jumper For Heat Staging s s H...

Страница 9: ...age of cooling Y1 and O are powered on and with second stage of cooling Y1 Y2 and O are on For these systems with first stage of heating Y1 is on and for second stage of heating Y1 and Y2 are on When...

Страница 10: ...There is no delay between staging from low to high and from high to low capacity The compressor will change from low to high and from high to low capacity on the fly to meet the demand DEFROST This c...

Страница 11: ...th Accessory Liquid Solenoid Using a Non Communicating Thermostat The liquid solenoid is connected to the Y1 and C terminal connections The liquid solenoid closes in the compressor off mode to prevent...

Страница 12: ...te fault code Compressor Thermal Cutout If the control senses the compressor voltage after start up and is then absent for 10 consecutive seconds while cooling demand exists the thermal protector is o...

Страница 13: ...ure If the outdoor ambient or coil thermistor should fail the control will flash the appropriate fault code see Table 6 IMPORTANT Outdoor air thermistor and coil thermistor are factory mounted in the...

Страница 14: ...INSTALLATION INSTRUCTIONS R 410A Split System Heat Pumps 14 428 01 1703 01 Specifications subject to change without notice Figure 14 Two Stage Control Board...

Страница 15: ...ault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check w...

Страница 16: ...10A as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig...