Day and Night CCH9 Скачать руководство пользователя страница 5

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pumps

428 01 1703 01

5

Specifications subject to change without notice.

Outdoor Unit Connected to Factory Approved 

Indoor Unit

These outdoor units are carefully evaluated and listed with

specific indoor coils for proper system performance.

Install Adapter Tube

1. Remove plastic retainer holding outdoor piston in liquid

service valve.

2. Check outdoor piston size with matching number listed

on unit rating plate.

3. Locate plastic bag taped to unit containing adapter

tube.

4. Remove Teflon

®

 seal from bag and install on open

end of liquid service valve. (See Fig. 3.)

5. Remove adapter tube from bag and connect threaded

nut to liquid service valve. Tighten nut finger

tight and

then with wrench an additional 1/2 turn (15 ft

lb). 

DO

NOT OVER TIGHTEN!

Figure 3

Liquid Service Valve

Install Liquid Line Filter Drier Indoor

Refer to Fig. 4 and install filter drier as follows:

1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to  5 in. (127 mm) liquid  tube from

step 1.

4. Connect and braze liquid refrigerant tube to the filter

drier.

Figure 4

Liquid Line Filter Drier

Refrigerant Tubing and Sweat Connections

Use refrigerant grade tubing. Service valves are closed from

factory and ready for brazing. After wrapping service valves

with a wet cloth, braze sweat connections using industry

accepted methods and materials. Consult local code

requirements. Refrigerant tubing and indoor coil are now

ready for leak testing . This check should include all field and

factory joints.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat

sinking

material such as a wet cloth while brazing.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Installation of filter drier in liquid line is  required.

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using

the recommended deep vacuum method of 500 microns. An

alternate triple evacuation method may be used.

IMPORTANT

: Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable

of pulling a vacuum of 500 microns and a vacuum gage

capable of accurately measuring this vacuum depth. The

deep vacuum method is the most positive way of assuring a

system is free of air and liquid water. (See Fig.5)

Figure 5

Deep Vacuum Graph

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MICRONS

2500

3000

3500

4000

4500

5000

A95424

Triple Evacuation Method

The triple evacuation method should only be used when

system does not contain any water in liquid form and vacuum

pump is only capable of pulling down to 28 inches of mercury

(711mm Hg). Refer to Fig. 6 and proceed is as follows:

1. Pull system down to 28 inches of mercury (711mm Hg)

and allow pump to continue operating for an additional

15 minutes.

2. Close manifold valves or valve at vacuum pump and

shut off vacuum pump.

3. Connect a nitrogen cylinder and regulator to system

and fill with nitrogen until system pressure is 2 psig.

Содержание CCH9

Страница 1: ...hanced installation reliability or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manu...

Страница 2: ...d refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube...

Страница 3: ...ctions from kit for installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent damage to the unit ensure that it is located...

Страница 4: ...ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 2...

Страница 5: ...E HAZARD Failure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DA...

Страница 6: ...d Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to fol...

Страница 7: ...ment size See Observer Wall Control Installation Instructions and indoor specification sheet for available adjustments Airflow Setup with Non Communicating Furnace or Fan Coil Two stage compressor ope...

Страница 8: ...age 1 Heat Stage 3 Heat Cool Stage 2 Fan 24 VAC Hot Dehumidify 24 VAC Comm Humidify RVS Heating Outdoor G O R W1 Y Y2 C Y1 W2 H O Y1 Y2 C W1 Two Stage Heat Pump Remove J2 Jumper For Heat Staging s s H...

Страница 9: ...age of cooling Y1 and O are powered on and with second stage of cooling Y1 Y2 and O are on For these systems with first stage of heating Y1 is on and for second stage of heating Y1 and Y2 are on When...

Страница 10: ...There is no delay between staging from low to high and from high to low capacity The compressor will change from low to high and from high to low capacity on the fly to meet the demand DEFROST This c...

Страница 11: ...th Accessory Liquid Solenoid Using a Non Communicating Thermostat The liquid solenoid is connected to the Y1 and C terminal connections The liquid solenoid closes in the compressor off mode to prevent...

Страница 12: ...te fault code Compressor Thermal Cutout If the control senses the compressor voltage after start up and is then absent for 10 consecutive seconds while cooling demand exists the thermal protector is o...

Страница 13: ...ure If the outdoor ambient or coil thermistor should fail the control will flash the appropriate fault code see Table 6 IMPORTANT Outdoor air thermistor and coil thermistor are factory mounted in the...

Страница 14: ...INSTALLATION INSTRUCTIONS R 410A Split System Heat Pumps 14 428 01 1703 01 Specifications subject to change without notice Figure 14 Two Stage Control Board...

Страница 15: ...ault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check w...

Страница 16: ...10A as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig...

Отзывы: