Day and Night CCH9 Скачать руководство пользователя страница 3

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pumps

428 01 1703 01

3

Specifications subject to change without notice.

Clearance Requirements

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 24 in. (610 mm)

clearance to service end of unit and 48 in. (1219.2 mm)

above unit. For proper airflow, a 6 in. (152.4 mm)  clearance

on one side of unit and 12 in. (304.8 mm) on all remaining

sides must be maintained. Maintain a distance of 24 in.

(609.6 mm) between units. Position so water, snow, or ice

from roof or eaves cannot fall directly on unit.

Figure 2

Tie Down Knockouts

3/8-in. (9.53 mm) Dia.

Tiedown Knockouts in

Basepan(2) Places

View From Top

UNIT BASE PAN

Dimension

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

35 X 35

9–1/8 (231.8)

6–9/16 (166.7)

28–7/16 (722.3)

On rooftop applications, locate unit at least 6 in. (152.4 mm)

above roof surface.

Operating Ambient

The minimum outdoor operating ambient  in cooling mode is

55

°

F (12.78

C), and the maximum outdoor operating ambient

in cooling mode is 125

°

F (51.67

C). At line voltage of 208V

(or below) and an outdoor ambient of 120

°

F (48.9

°

C) (and

above), the compressor operates in low stage The maximum

outdoor operating ambient in  heating mode  is 66

°

F

(18.89

C). 16 SEER product is approved for low ambient

cooling operation down to an ambient as low as 0

°

F

(

17.78

C) with low ambient accessory kits. 19 SEER

product is not approved for low ambient cooling applications.

Elevate Unit

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Unit must be kept free of an accumulation of water and/or

ice in the basepan.

Elevate unit per local climate and code requirements to

provide clearance above estimated snowfall level and ensure

adequate drainage of unit. If using accessory support feet,

use installation instructions from kit for installation.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
To prevent damage to the unit, ensure that it is located

with the supports such that the unit is stable in all

circumstances including adverse conditions.

Make Piping Connections

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could result in personal

injury or death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal.
Use all service ports and open all flow

control devices,

including solenoid valves.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not leave system open to atmosphere any longer than

minimum required for installation. POE oil in compressor is

extremely susceptible to moisture absorption. Always keep

ends of tubing sealed during installation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4

mm) vertical rise at service valve.  Refrigerant tubing

lengths up to 36 in. (914.4 mm) may be buried without

further special consideration.  Do not bury lines more than

36 in. (914.4 mm).

!

WARNING

PERSONAL DAMAGE HAZARD

Failure to follow this warning may result in equipment

damage or improper operation.
To prevent damage to unit or service valves, observe the

following:

 

Use a brazing shield.

 

Wrap service valves with wet cloth or use a heat sink

   material.

Outdoor units may be connected to indoor section using

accessory tubing package or field

supplied refrigerant grade

tubing of correct size and condition. For tubing requirements

beyond 80 ft/24.38 m, substantial capacity and performance

losses can occur. Following the recommendations in the

Long Line Applications Guideline will reduce these losses.

Refer to Table 1 for accessory requirements. Refer to Table 2

for field tubing diameters.
If refrigerant tubes or indoor coil are exposed to atmosphere,

they must be evacuated to 500 microns to eliminate

contamination and moisture in the system.

Содержание CCH9

Страница 1: ...hanced installation reliability or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manu...

Страница 2: ...d refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube...

Страница 3: ...ctions from kit for installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent damage to the unit ensure that it is located...

Страница 4: ...ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 2...

Страница 5: ...E HAZARD Failure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DA...

Страница 6: ...d Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to fol...

Страница 7: ...ment size See Observer Wall Control Installation Instructions and indoor specification sheet for available adjustments Airflow Setup with Non Communicating Furnace or Fan Coil Two stage compressor ope...

Страница 8: ...age 1 Heat Stage 3 Heat Cool Stage 2 Fan 24 VAC Hot Dehumidify 24 VAC Comm Humidify RVS Heating Outdoor G O R W1 Y Y2 C Y1 W2 H O Y1 Y2 C W1 Two Stage Heat Pump Remove J2 Jumper For Heat Staging s s H...

Страница 9: ...age of cooling Y1 and O are powered on and with second stage of cooling Y1 Y2 and O are on For these systems with first stage of heating Y1 is on and for second stage of heating Y1 and Y2 are on When...

Страница 10: ...There is no delay between staging from low to high and from high to low capacity The compressor will change from low to high and from high to low capacity on the fly to meet the demand DEFROST This c...

Страница 11: ...th Accessory Liquid Solenoid Using a Non Communicating Thermostat The liquid solenoid is connected to the Y1 and C terminal connections The liquid solenoid closes in the compressor off mode to prevent...

Страница 12: ...te fault code Compressor Thermal Cutout If the control senses the compressor voltage after start up and is then absent for 10 consecutive seconds while cooling demand exists the thermal protector is o...

Страница 13: ...ure If the outdoor ambient or coil thermistor should fail the control will flash the appropriate fault code see Table 6 IMPORTANT Outdoor air thermistor and coil thermistor are factory mounted in the...

Страница 14: ...INSTALLATION INSTRUCTIONS R 410A Split System Heat Pumps 14 428 01 1703 01 Specifications subject to change without notice Figure 14 Two Stage Control Board...

Страница 15: ...ault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check w...

Страница 16: ...10A as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig...

Отзывы: