5. Connecting
5.1. Preparing the connection
Select connection
cable
Preparing cables
Always observe the following safety instructions:
•
The connection must be carried out by trained and authorized
personnel only!
•
Connect or disconnect only in the complete absence of line voltage
•
You should take note the data concerning on the overcurrent
protection in installation.
•
Use only a screwdriver with appropriate head
Take note the suitability of the connecting cable
(wire cross-section, insulation, screening, etc.).
You may use either solid conductor or flexible conductor.
In case of using flexible conductor use crimped wire end.
The instrument can be connected with standard two-wire cable
without screen.
If electromagnetic interference is expected which is above the test
values of the correspondent standard for industrial areas (e.g. high
power frequency drives are working in the area) screened cable
should be used. Ground the cable shield on the cabinet side.
Always lead the signal cables on a separate path from the control and
power cables!
Prepare the cable for the connection. Strip approx. 8 mm insulation.
In case of using flexible conductor use crimped wire end.