DT1010 xx xx
20180403-V1
15
6. The first start-up, indicators
6.1. The first start-up
After
connecting
the
DT1010
xx
xx is ready to work with the
factory default parameters.
When you are going to use other parameters you should
set-up the instrument according to Chapter 7.
Factory default settings:
•
Sensor connecting 4 wire.
•
Measuring mode: temperature measurement.
•
Current output: 4
-
20 mA.
•
Current output error value: 3.2 mA.
•
Averaging: 16 measurement.
•
Output refresh time: 0.5 sec.
•
Sensor characteristics fitting mode: off.
•
Output scaling: -200.0 °C ÷ 4 mA-t; +800.0 °C ÷ 20 mA.
•
Password:”1000”.
•
Wire resistance in 2 wire connecting: 0 Ohm.
•
Potentiometer measurement mode and scaling:
0% ÷ 0.00, 100% ÷ 100.00. (for potentiometer measurement
first you should calibrate the potentiometer according:
Chapter 7.)