iBoot-30A
Page 14
iBoot-30a_v101118e
DxP
Port:
9100
Timeout:
2
set ipmode <static | dhcp>
This command sets the ip address setting mode. Static
mode locks the address as set, dhcp mode allows DHCP
server to assign address.
set ipaddress <dotted decimal>
This command is used to set the iB-30’s ip address.
192.168.1.254
set subnet <dotted decimal>
This command is used to set the iB-30’s subnet mask. 255.255.255.0
set gateway <dotted decimal>
This command is used to set the Gateway
192.168.1.1
set http port <0-65535>
This command sets the port that the iB-30’s web server
listens for incoming connections on. When set to 0 the
web server is disabled.
80
set telnet port <0-65535>
This command sets the port that the iB-30’s Telnet server
listens for incoming connections on. When set to 0 the
Telnet server is disabled
23
set dxp port <0-65535>
This command sets the port that the iB-30’s DxP protocol
service listens for incoming connections on. When set to
0 the Protocol service is disabled.
Note: At least one of the above MUST NOT be 0. The
CLI will protect against all 3 from being set to 0.
9100
set timeout <0-999>
This command sets the automatic network timeout in
minutes
2
AUTOPING COMMANDS
These commands require a reboot before they will take effect.
These commands are available to the administrator only.
get autoping
This command returns all of the AutoPing settings as
shown below.
AutoPing
1
AutoPing
2
IP
Address:
192.168.233.254
192.168.233.154
Frequency:
10
10
Fail
Count:
3
3
‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐
Mode:
Single
Action:
Cycle
Once
set autoping <1 | 2> ipaddress <dotted
decimal>
This command is used to set the IP address of AutoPing
1 or AutoPing 2
0.0.0.0
set autoping <1 | 2> frequency <1-999>
This command is used to set the frequency (how often
the iB-30 sends the ping) for each of the AutoPings.
10
set autoping <1 | 2> failcount <1-999>
This command is used to set the number of consecutive
failures the AutoPings must detect before the AutoPing
considers the pinged device to be failed.
3
set autoping mode <single | and | or>
Sets single AutoPing (AutoPing 1) or two AutoPing
relationship And or Or.
Single
set autoping action <none | on-latch | on-
follow | off-latch | off-follow | cycle | cycle-
once>
This command is used to set the action that the iB-30 will
perform when the autoping triggers.
None