background image

 
 
 

iBoot-30A 

 

   

Page 10 

iBoot-30a_v101118e

 

AutoPing Settings 

IP Address 1 and 2: Enter one or two the IP 
addresses of the device(s) to be pinged.   
 
Ping Frequency: Enter 1 to 999 seconds.  The 
ping will go out to the selected device this often. 
 
Fail Counter:  Enter 1-999 times the ping needs 
to fail consecutively before the selected action is 
taken.  When the fail count has been reached, 
the AutoPing action will be triggered. 
 
Mode:  Select from AND, OR or Single.  With 
And, both AutoPings need to exceed their fail 
count to trigger the Action.  With Or, the Action will be triggered if either AutoPing fails.  With Single, 
only AutoPing 1 is used.  If mode is Single, AutoPing 2 can still be used for display purposes only. 
 

Action:  Select from   

None 

AutoPing not used 

Power On – Latch 

Upon triggering, iB-30 will power on and remain so until changed via 
the web, telnet, DxP, etc. 

Power On – Follow 

Upon triggering, iB-30 will power on.  When the ping response 
returns, iB-30 will power off. 

Power Off – Latch 

Upon triggering, iB-30 will power off and remain so until changed via 
the web, telnet, DxP, etc. 

Power Off – Follow 

Upon triggering, iB-30 will power off.  When the ping response 
returns, iB-30 will power on. 

Power Cycle 

Upon triggering, iB-30 will cycle the power.  iB-30 will wait the Ping 
Frequency x Fail Count; if the response does not return, the power 
will be recycled again.  This will continue until the ping response 
returns or Auto Ping is turned off.  Make sure your Auto Ping 
frequency is longer than the time required to reboot your device. 

Power Cycle Once 

Upon triggering, iB-30 will cycle power one time. It will not cycle again 
automatically until the ping response returns and is lost again. 

 
With AutoPing operational, the main iB-30 page will display the current status of this feature.  The 
status will be OK to indicate that iB-30 is receiving responses to the ping, or that the fail counter has 
not yet been exceeded. 
 
If the fail count has been exceeded, the status will change to FAIL. The Fail Counter will indicate the 
number of times the failure has occurred, and the  Trigger Counter indicates the number of times the 
AutoPing action has been triggered.  A counter reset button is provided when logging in with the 
Admin password. 

AutoPing Setup Page 

Содержание iBoot-30A

Страница 1: ...ntents 1 Important Safety Instructions 2 General Description 3 Hardware Installation 4 Initial Configuration 5 Web Browser Operation 7 Web Setup 8 Command Line Interface 13 Firmware Upgrades 17 Troubl...

Страница 2: ...to 2 prong adapter at the receptacle use of this type adapter may result in risk of electrical shock and or damage to this product 9 Do not allow anything to rest on the power cord Do not locate this...

Страница 3: ...devices by keeping them powered off when not in use This prevents hackers from seeing them at all times Power down equipment when not needed for power savings and to save on wear and tear Power up ale...

Страница 4: ...ections enter the unit by selecting one or two of the larger knockouts similar to those used for the above network connection and installing the larger cable clamps All AC connections are made on the...

Страница 5: ...ess Make sure you have physical access to the iB 30 before attempting to set the IP Address The Setup Utility will only work with iBoots on the same local subnets as the PC Once the iB 30 Setup Utilit...

Страница 6: ...via the Set up Page 3 CLI Telnet iB 30 comes with factory installed IP address 192 168 1 254 If you network has a DHCP server it will automatically assign an IP address to iB 30 the first time it is c...

Страница 7: ...ck on the appropriate button During power cycling the Power Status bar will indicate the temporary status with a blue background Once the cycle is complete the status bar will revert to its original c...

Страница 8: ...Telnet and reboot the unit Web Setup iB 30 setup section consists of several pages Access any page via the buttons on the left of the page Each time a setting is changed click on the Save button for t...

Страница 9: ...30 Upon Clicking Reboot the Googbye page is displayed with a link to re login AutoPing Settings The AutoPing feature allows iB 30 to automatically detect failed equipment and perform a timed reboot or...

Страница 10: ...remain so until changed via the web telnet DxP etc Power Off Follow Upon triggering iB 30 will power off When the ping response returns iB 30 will power on Power Cycle Upon triggering iB 30 will cycle...

Страница 11: ...e zone relative to GMT Once the time server is active scheduled events can occur Up to eight independent scheduled events can be programmed Date Set the initial date for the event The format for the d...

Страница 12: ...used the main screen will not have a link to Setup The Administrator Password allows access to both the Main Screen and the Setup Screen Passwords can be up to 20 characters long and are case sensitiv...

Страница 13: ...y Default CONTROL COMMANDS These commands are used to monitor and control the outlet set outlet on off cycle This command controls the outlet get outlet This command returns the current status of the...

Страница 14: ...The CLI will protect against all 3 from being set to 0 9100 set timeout 0 999 This command sets the automatic network timeout in minutes 2 AUTOPING COMMANDS These commands require a reboot before the...

Страница 15: ...es no This command enables or disables the use of the time server and scheduled events No get time Displays the current time and time server Current Time 16 10 41 01 27 2010 Server 64 90 182 55 set ev...

Страница 16: ...iBoot 30A Page 16 iBoot 30a_v101118e prompt will remain the active prompt until the iB 30 has been rebooted...

Страница 17: ...lable at the link above If the iBoot you would like to upgrade is not visible in the list box either Select Device Discover from the menu to locate iB 30 units on the local network or Select Device Ad...

Страница 18: ...nal blocks or AC wiring when the unit is connected to the AC power source Use the pushbutton as follows Action Result Momentary Soft Reset Will not change outlet status 5 Seconds push Reset to Factory...

Страница 19: ...Max at 210 240 VAC Compliance CE Directives 89 336 EEC 92 31 EEC and 93 68 EEC EN 60950 3rd Edition EN 55022 1998 Class B FCC Part 15 Class B Network Dual 10 100 Unshielded Twisted Pair Ethernet Jacks...

Страница 20: ...chnical Service at 201 934 5111 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shipm...

Отзывы: