background image

 
 

COE-8 

 

Page 2 

Hardware Installation 

 
Inputs (COE-8

I

)  

Connect the inputs to the COE-8

I

 using the screw terminals on 

the printed circuit card, as illustrated.  Inputs can be either dry 
relay or switch contacts, or a +VDC voltage (3 to 30 V), 
referenced to a common ground.   
 

Status 

Dry Relay 

DC Voltage 

Open 

Open 

>3VDC  

Closed 

Closed 

<=0VDC 

 
Input Specification 

Dry Contact (common ground) 

 

 

 

or Wet ±30VDC Max

 

 
 
 
 
 
 
 

Relays (COE-8O) 

Connect the inputs to the COE-8I using the screw terminals on 
the printed circuit card, as illustrated.  Relays are Form A. 
 
Relay Specifications 
 

Rating (resistive) 

 

0.5 A 120 VAC or 1 A 24 VDC 

Maximum Carrying Current  

2 A 

Maximum Switching Power  

60 AV, 24 W 

Maximum Switching Voltage  

120 VAC/60 VDC 

Maximum Switching Current  

1A

 

Life Expectancy:  

 

 5 Million Operations Mechanical    

 

 

 

 

100K Operations at rated load 

 
 

 

Network 

Connect the network to the connector provided.  A yellow LED 
indicates a successful connection to the network, a green LED 
data activity. 

Power 

Apply power only when the cover is secured onto the COE-8.  Use 
only the wall mounted power supply provided.  For applications 
outside the US use Dataprobe Power Supply 1930044. 

 

COE-8 VERSION 2 INPUT

DATAPROBE

5

GND

MADE IN U.S.A.

DRY OR +3 TO +30VDC

INPUTS

GND

GND

7

6

GND

GND

8

4

GND

3

GND

2

1

GND

1

7-0142303-001 REV B

RELAY OUTPUT

7-0142303-002 REV B

8

N.O.

COE-8 VERSION 2 OUTPUT

6

7

1

2

4

5

3

MADE IN U.S.A.

DATAPROBE

J1

Содержание COE-8

Страница 1: ...O has eight relays that will mirror the status of the eight inputs of the COE 8I Each unit can be monitored and configured from a Web Browser Each channel of the COE 8I is independently configurable a...

Страница 2: ...DC Maximum Carrying Current 2 A Maximum Switching Power 60 AV 24 W Maximum Switching Voltage 120 VAC 60 VDC Maximum Switching Current 1A Life Expectancy 5 Million Operations Mechanical 100K Operations...

Страница 3: ...p the COE 8 units WEB Page Access The web pages provide status information on the inputs and outputs of the COE 8 as well as provide configuration for the unit Open a browser to the default or current...

Страница 4: ...Subnet Mask and Gateway as provided by your network administrator Click Apply to save the changes You will then be prompted to reboot the COE 8 Click on the Reboot button The COE 8 will reboot and the...

Страница 5: ...for web browser access that port must specifically be used in the URL when accessing the COE 8 For example if the Web Port is changed to 9090 then the URL for the unit would be http 192 168 1 254 9090...

Страница 6: ...there is a change of state on any COE 8 channel Check the box provided to enable this If both the COE 8I and COE 8O are configured to send traps two messages will be received by each SNMP manager for...

Страница 7: ...967 8788 to receive a Return Materials Authorization RMA Number prior to sending any equipment back for repair Include all cables power supplies and proof of purchase with shipment THIS WARRANTY DOES...

Отзывы: