Hardware Installation
Inputs (COE-8
I
)
Connect the inputs to the COE-8
I
using the screw terminals on
the printed circuit card, as illustrated. Inputs can be either dry
relay or switch contacts, or a +VDC voltage (3 to 30 V),
referenced to a common ground.
Status
Dry Relay
DC Voltage
Open
Open
>3VDC
Closed
Closed
<=0VDC
Input Specification
Dry Contact (common ground)
or Wet ±30VDC Max
Relays (COE-8O)
Connect the inputs to the COE-8I using the screw terminals on
the printed circuit card, as illustrated. Relays are Form A.
Relay Specifications
Rating (resistive)
0.5 A 120 VAC or 1 A 24 VDC
Maximum Carrying Current
2 A
Maximum Switching Power
60 AV, 24 W
Maximum Switching Voltage
120 VAC/60 VDC
Maximum Switching Current
1A
Life Expectancy:
5 Million Operations Mechanical
100K Operations at rated load
Network
Connect the network to the connector provided. A yellow LED
indicates a successful connection to the network, a green LED
data activity.
Power
Apply power only when the cover is secured onto the COE-8. Use
only the wall mounted power supply provided. For applications
outside the US use Dataprobe Power Supply 1930044.