LOW VOLTAGE ELECTRICAL CONNECTIONS

8

   PWR-240B

DC OK Monitoring

The DC voltage terminal block provides two wiring terminals (13-14), which monitor the

status of the switching power supply (DC OK feature). When the power supply module

runs correctly, lines 13 and 14 form a normally closed contact.  If the power module

experiences problems (i.e. output overload causing output voltage to be reduced by less

than 90% of nominal) these lines open. Lines 13 and 14 are decoupled from the power

output lines and can be connected to a free digital input to signal this alarm condition.

DC Direct Output

The 24 volt DC Output terminals are direct. Connect the output devices according to

your application requirements.

LASER BARCODE SCANNERS

Supply Capacity When Wiring Directly to AS-I Compatible Scanners

For direct wiring, power distribution is performed simultaneously for all the scanners.

However all the scanner motors start up slowly so that there is no significant peak cur

-

rent draw. See the specific scanner manual for consumption data.

The maximum number of same type scanners to be supplied for direct wiring the PWR-

240B is shown in the table below and depends on the wiring topology:

The following products are also AS-I compatible: DS5100, DM3610, SC5000. In case of

networks using a mix of products, you must calculate the total power consumption so as

not to exceed the limits for the specific topology used. See the specific product refer

-

ence manual in the Technical Features chapter for consumption data.

The power supply unit is connected directly to the scanners via AS-I cabling.

SCANNER TYPE

MAXIMUM NUMBER OF SCANNERS BY 

TOPOLOGY

DOUBLE BRANCH

SINGLE BRANCH

DS8110

11 (balanced 6+5)

9

DX8210

11 (balanced 6+5)

9

AS-I Single Branch

200 W max

AS-I Double Branch

240 W max total (200 W max for a single branch)

Содержание PWR-240B

Страница 1: ...PWR 240B INSTALLATION MANUAL Reading Station Power Supply...

Страница 2: ...ion and shall ensure that all notices appear on any reproductions of the documentation Electronic versions of this document may be downloaded from the Datalogic website www data logic com If you visit...

Страница 3: ...TALLATION 5 Cabinet Mounting 5 CHAPTER 4 LOW VOLTAGE ELECTRICAL CONNECTIONS 6 DC Low Voltage Cable Insertion 6 Cable Entry Plate 6 AS I Cable Insertion 7 DC Voltage Terminal Block 7 DC OK Monitoring 8...

Страница 4: ...to download Data Sheets Manu als Software Utilities and Drawings Hover over the Support Service menu for access to Services and Technical Support Reseller Technical Support An excellent source for te...

Страница 5: ...conformity is a living document The EU declaration of conformity is available for competent authorities and customers through Datalogic commercial reference contacts Since April 20th 2016 the main Eur...

Страница 6: ...Key Lock 6 Cooling Fan 2 Product Data Label 7 AC Line Input Terminal Block 3 AC Input Cable Compression Connector 8 Thermal magnetic Circuit Breaker 4 Cable Entry Plate with Grommets 9 DC OK Terminal...

Страница 7: ...direct connection block The direct connection block is protected by the internal power supply features Two output power supply status monitoring signals DC OK are provided to connect to an optional di...

Страница 8: ...s a reduction in voltage below 13V This causes the power supply to enter HICCUP operation where power is supplied for 2 seconds and then shuts off for 18 seconds This procedure is repeated until the s...

Страница 9: ...lication Barcode Scanners Correctly connect the AS I cabling to the PWR using the AS I cable wiring instruc tions for backbone and branch wiring See Laser Barcode Scanners on page 8 and your scanner m...

Страница 10: ...2 3 the AC input cable must have a maxi mum diameter of 14mm and the conduit a max diameter of 16mm 5 With AC line voltage OFF wire the AC Line to the AC Line Input Terminal Block see AC Line Input Vo...

Страница 11: ...unt the bracket to the cabinet 2 Mount the cabinet to the frame Figure 5 Mounting Brackets Figure 6 PWR 240B cabinet max height Please note that the cabinet door can be unlocked and opened by using th...

Страница 12: ...he Cable Entry Plate and select all the necessary grommets for your application 3 Insert the correct size sealing grommets and positions relative to these cables Unused positions must mount the closed...

Страница 13: ...sitioning Strip the individual wires for insertion into the Terminal Block Figure 7 AS I Cable Prep Pass the AS I cable through the AS I cable sealing grommet and make sure there is enough length to e...

Страница 14: ...iring power distribution is performed simultaneously for all the scanners However all the scanner motors start up slowly so that there is no significant peak cur rent draw See the specific scanner man...

Страница 15: ...240B Directly to Scanners Refer to the specific scanner manual for I O interface wiring connections AS I Wiring Topologies Figure 11 Single Branch Topology 24 Vdc to scanners using AS I cabling DC OK...

Страница 16: ...Y INDUSTRIAL ETHERNET SWITCH An accessory 24 Vdc Industrial Ethernet Switch can be installed and powered from inside the PWR 240B power supply Figure 13 24 Volt Industrial Ethernet Switch device nodes...

Страница 17: ...UAL 11 Fix the Industrial Ethernet Switch to the DIN rain using the clips provided inside the PWR and connect the power cables as shown in the figure below Figure 14 Industrial Ethernet Switch Mounted...

Страница 18: ...sconnector and Distributor cabinet which provides this protection For primary wiring use a 3 conductor cable between 2 5 mm2 4 mm2 13 AWG 11 AWG for every conductor Choose the overall cable diameter a...

Страница 19: ...PWR 240B AC Line Terminal Block with Protection Covers The terminal block marked with the ground symbol is a special block which allows direct connection of the Protection Earth with the enclosure of...

Страница 20: ...er Block The DC Power Block connects to the AC input line and Its AC cord must be adapted to connect to the PWR AC input terminal block Cut the power block AC cord to about 30 cm 12 in from the female...

Страница 21: ...ALLATION MANUAL 15 Figure 18 Fixing the 12 Vdc Power Block inside the PWR 240B Pass the 12 Vdc output cable through the correct size grommet in the cable entry panel holder pass two tie wraps under ne...

Страница 22: ...Current Consumption Max 6 A Icp 10kA output at full load Output Voltage 24 Vdc Nominal Output Current 10 A Max Continuous Overcurrent 12 A up to 45 C ambient temp ENVIRONMENTAL FEATURES Operating Tem...

Страница 23: ...INSTALLATION MANUAL 17 APPENDIX A ELECTRICAL DIAGRAMS PWR 240B ELECTRICAL DIAGRAM The PWR 240B components are electrically connected as displayed in the following dia gram...

Страница 24: ...m AK1 DIN BAR LINE PE LINE N LINE L 4 0 mm 4 0 mm F0 N L 6 A DIN BAR 2 5 mm 2 5 mm N01 L01 N01 L01 L01 N01 2 5 mm 2 5 mm 2 5 mm T10 1 0 mm 1 0 mm 4 0 mm 4 0 mm 0 2 mm 0 2 mm T10 ALARM 13 T10 ALARM 14...

Страница 25: ......

Страница 26: ...yright no part of this documentation may be repro duced stored in or introduced into a retrieval system or transmitted in any form or by any means or for any purpose without the express written permis...

Отзывы: