OPERATING FEATURES
2
PWR-240B
cannot cause overload conditions since they are equipped with intrinsic power monitor
-
ing systems. The AIR CLEANING SYSTEM fans also have this function.
Figure 3 - Overload Behavior
Heavy Overload (including short-circuit)
Heavy Overload is defined as application of a load which causes a reduction in voltage
below 13V. This causes the power supply to enter HICCUP operation where power is
supplied for 2 seconds and then shuts off for 18 seconds. This procedure is repeated
until the short-circuit or overload is resolved, see Figure 4
Short-Circuit Protection HIC
-
CUP Mode
. For this condition, the maximum length of the power cables between the
power supply and the powered devices guarantees the behavior of a short-circuit down
-
stream of this cable.
Figure 4 – Short-Circuit Protection HICCUP Mode