GETTING STARTED
5
1
1.5.4 Maximum Supported Trunk and Drop Cable Lengths
ThickNet trunk length up to 300 m.
ThinNet trunk length up to 20 m.
ThinNet drop cable length up to 2 m.
1.6 INSTALLING THE GATEWAY
The numbered steps in the following procedure are also indicated in the SubNet16 networks
example layouts shown in Appendix B.
1. Preliminary Notes
: Read the Installation Guidelines in par. 1.5.
2. Mounting
: Mount the Gateway to your chosen location using two M5 (#10) screws,
lock washers and nuts. The Gateway may be mounted in any orientation, but should
be aligned in such a manner that the LED indicators can be seen during operation.
3. Gateway Connection
: Attach one end of a 5-pin, male-to-male, M12, ThinNet drop
cable (
P/N: CBL-1481-XX
) to the 5-pin, female, M12 connector on the Gateway.
Connect the other end of this 5-pin, male-to-male, M12, ThinNet drop cable to the 5-
pin, female, M12 connector on EITHER a
ThickNet to ThinNet Drop-T Connector
OR a
ThinNet to ThinNet Drop-T Connector
(as per your network and RFID
application requirements).
4. Trunk Wiring
: Attach one end of a male-to-female trunk cable to each mating
connector on the Drop-T Connector. Continue connecting trunk cables and Drop-T
connectors as needed.
Note: trunk length should not exceed 300 m for ThickNet and 20 m for ThinNet.
5. RFID Controller Connection
: Connect the male end of a 5-pin, male-to-female,
ThinNet drop cable to the female end on your Drop-T connector(s). Attach the
remaining female end of the ThinNet drop cable to the 5-pin, male, M12 connector on
a
Cobalt UHF
,
Cobalt HF
or
C-Series Controller (RS485 models)
. Repeat
Step 5
for each RFID controller you plan to install.
Note: maximum drop cable length is 2 m.
6. Termination Resistors
: For ThickNet Networks: Connect a Terminating Resistor
(
P/N: CBL-1489,
male)
or
(P/N: CBL-1497, female)
to the first and last Drop-T
Connector on the trunk line.
For ThinNet Networks: Connect a Terminating Resistor (
P/N: CBL-1490,
male)
or
(P/N: CBL-1496, female)
to the first and last Drop-T Connector on the trunk line.
7. Power Supply Wiring
: For ThickNet Networks: Using a 5-pin, female, 7/8 - 16,
ThickNet to Bare Wire Leads cable (
P/N: CBL-1495-XX
), connect the bare wires to
your power supply (SHIELD wire connected to Earth). Attach the female, ThickNet
end to the 5-pin, male, ThickNet end on a Drop-T connector (
P/N: CBL-1526)
.
For ThinNet Networks: Using a 5-pin, female, M12, ThinNet to Bare Wire Leads cable
(
P/N: CBL-1494-XX
), connect the bare wires to your power supply (SHIELD wire
connected to Earth). Attach the female, ThinNet end to the 5-pin, male, ThinNet end
on a Drop-T connector (
P/N: CBL-1486)
.