5.3 ID-NET™ INTERFACE
25-pin Name
Function
23
ID+
ID-NET™ n
24
ID-
ID-NET™ network -
7 GND
Ground
5.3.1 ID-NET™
Cables
The following instructions are referred to Figure 70, Figure 71 and Figure 72.
The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted
pair, shielded cable AWG 24 (or AWG 22) stranded flexible.
We recommend using DeviceNet cables (drop or trunk type) to the following reference
standards:
AN50325 – IEC 62026
UL STYLE 2502 80°C 30V
Cable Shield MUST be connected to earth ground ONLY at the Master.
NEVER use ID-NET™ cable shield as common reference.
The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table
below).
For Common Power Connections use only 2 wires (23 and 24).
-
DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do not
put it together with AC cable):
-
Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8
Volts.
-
Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide loops
between them).
Scanner's chassis may be connected to earth.
Network inside the same building.
Baudrate Table
Baud Rate
125 kbps
250 kbps
500 kbps
1Mbps
Cable Length
1200 m
900 m
700 m
*
* Application dependent, contact your Datalogic Automation representative for details.
NOTE
The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates
allow longer cable lengths. The baudrate is software configurable by
authorized Datalogic Automation personnel only.
Содержание DS2100N
Страница 1: ...DS2100N Reference Manual ...
Страница 20: ...DS2100N REFERENCE MANUAL 10 1 b Operating mode selection and definition c Digital Outputs configuration ...
Страница 54: ...DS2100N REFERENCE MANUAL 44 4 Figure 46 ID NET Network Connections with isolated power blocks ...
Страница 55: ...CBX ELECTRICAL CONNECTIONS 45 4 Figure 47 ID NET Network Connections with Common Power Branch Network ...
Страница 56: ...DS2100N REFERENCE MANUAL 46 4 Figure 48 ID NET Network Connections with Common Power Star Network ...
Страница 69: ...25 PIN CABLE ELECTRICAL CONNECTIONS 59 5 Figure 68 DS2100N Multidrop Connection to a Multiplexer ...
Страница 72: ...DS2100N REFERENCE MANUAL 62 5 Figure 70 ID NET Network Connections with isolated power blocks ...
Страница 73: ...25 PIN CABLE ELECTRICAL CONNECTIONS 63 5 Figure 71 ID NET Network Connections with Common Power Branch Network ...
Страница 74: ...DS2100N REFERENCE MANUAL 64 5 Figure 72 ID NET Network Connections with Common Power Star Network ...
Страница 119: ...www datalogic com ...