DKM-411 User Manual Rev_01 Firmware V-1.0
K46D03-EN - 67 -
The parameters below define the functions of relay outputs. The unit has 2 relay outputs. Each relay has
programmable functions, selected from a list.
OUTPUT FUNCTION LIST
Number Function
Description
00
Horn
Alarm relay output. Turns off automatically when timer expired.
01
Flashing Relay
Bistable relay output. Periodically activates/deactivates with
programmed interval.
02
Phase Order Failure
Active when the phase order is reversed.
03
Voltage Fail
Active if at least one voltage is outside limits.
04
Voltage OK
Active if all voltages are within limits
05
Internal alarm
Active if any measurements based alarm exists
06
Input alarm
Active if any alarm caused by digital inputs exists
07
Warning
Active if any warning exists
08
Internal or Input alarm
Active if any alarm exists
09
kWh tick
kWh tick pulse output. Pulse length is programmable.
10
kVArh tick
kVArh tick pulse output. Pulse length is programmable.
11
Low Voltage Alarm
Active if at least one voltage is below low limit.
12
High Voltage Alarm
Active if at least one voltage is above high limit.
13
Low Frequency Alarm
Active if the frequency is below low limit.
14
High Frequency Alarm
Active if the frequency is above high limit.
15
Frequency Alarm
Active if the frequency is outside of limits.
16
Low Active Power
Active if the total kW is below low limit.
17
High Active Power
Active if the total kW is above high limit.
18
Active Power Alarm
Active if the kW is outside of limits.
19
Capacitive Reactive Power
Active if the capacitive reactive power is above high limit.
20
Inductive Reactive
Active if the inductive reactive power is above high limit.
21
Reactive Power Alarm
Active if capacitive or inductive reactive power is above limits.
22
Capacitive PF alarm
Active is the capacitive PF value is below limit.
23
Inductive PF alarm
Active is the inductive PF value is below limit.
24
PF alarm
Active if capacitive or inductive PF is below limits.
25
High Current Alarm
Active if at least one phase current is above limit.
26
THD-V Alarm
Active if at least one voltage THD is above limit.
27
THD-I Alarm
Active if at least one phase current THD is above limit.
28
THD Alarm
Active if any THD is above limit.
29
Voltage Unbalance
Active if the voltage unbalance is above limit.
30
Current Unbalance
Active if the current unbalance is above limit.
31
Unbalance Alarm
Active if the voltage or current unbalance is above limit.
32-39
User Input Alarm 1
…8
Active when the related user defined function is active.
40-43
Button 1
…4 Simulation
Active when related pushbutton is pressed.
44-45
Input 1
…2 Simulation
Active if signal received from related input.
20.5. OUTPUT CONFIGURATION
Содержание DKM-411
Страница 31: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 31 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR...
Страница 34: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 34 4 8 1 PHASE 2 WIRE...
Страница 35: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 35 5 CONNECTION DIAGRAM...
Страница 41: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 41...