DKM-411 User Manual Rev_01 Firmware V-1.0
K46D03-EN - 59 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
LCD Backlight
%
3
100
100
The intensity of the LCD back light.
Language
-
0
1
0
0:
English language selected.
1:
Local language selected. This
language may be downloaded.
Intermittent Alarm Timer
-
0
255
1
0:
continuous alarm (horn) output
1..255:
intermittent alarm output period
in seconds
Alarm Relay Timer
sec
0
120
60
The period during which the
ALARM
relay is active. If the period is set to 0,
the alarm output is constantly on.
Status Prompt Window
Enable
-
0
1
0
0:
Status prompts disabled
1:
Status prompts enabled
Modem Selection
-
0
1
0
0:
not used
1:
external GSM Datakom modem
SMS Enable
-
0
1
0
0:
SMS messages disabled
1:
SMS messages enabled
GPRS Connection
Enable
-
0
1
0
0:
GPRS disabled
1:
GPRS enabled
Web Refresh Rate
sec
0
240
5
The unit will refresh the web page with
this interval.
RS-485 Enable
-
0
1
1
0:
RS-485 port disabled
1:
RS-485 port enabled
Modbus Address
-
0
240
1
Modbus controller identity used in
Modbus communication.
RS-485 Baud Rate
bps
2400 115200
9600
This is the data rate of the RS-485
Modbus port.
Ethernet Enable
-
0
1
1
0:
ethernet port disabled
1:
ethernet port enabled
Real Time Clock Adjust
-
0
255
117
This parameter trims precisely the real
time clock circuit. Values from 0 to 63
speed up the clock with 0.25sec/day
steps. Values from 127 to 64 slow down
the clock with 0.25sec/day steps.
Periodic event time
min
1
65000
60
This parameter adjusts the period for
periodic event logging.
Intermittent Alarm Relay
Enable
-
0
1
0
0:
steady alarm output
1:
intermittent alarm output
SMS on Output Change
-
0
1
0
This parameter controls SMS sending
when any output has changed state. No
warnings generated.
0:
no SMS on output change
1:
SMS sent on output change
Alarm Event Log Enable
-
0
1
1
0:
No event logging on alarm
1:
Event logged on alarm condition
Warning Event Log
Enable
-
0
1
1
0:
No event logging on warning
1:
Event logged on warning condition
20. PROGRAM PARAMETER LIST
20.1. CONTROLLER CONFIGURATION GROUP
Содержание DKM-411
Страница 31: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 31 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR...
Страница 34: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 34 4 8 1 PHASE 2 WIRE...
Страница 35: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 35 5 CONNECTION DIAGRAM...
Страница 41: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 41...