DKM-411 User Manual Rev_01 Firmware V-1.0
K46D03-EN - 62 -
Reactive Capacitive
Power High Alarm Limit
kVAr
0
9’999
0
If the reactive capacitive power goes
over this limit, this will generate a
HIGH REACTIVE POWER alarm.
Reactive Inductive Power
High Alarm Limit
kVAr
0
9’999
0
If the reactive inductive power goes
over this limit, this will generate a
HIGH REACTIVE POWER alarm.
Reactive Power Alarm
Duration
sec
0
255
30
When the reactive power is outside
limits, the active power alarm will occur
after this timer.
Reactive Power Alarm
Lock Enable
-
0
1
0
0:
reactive power alarm disappears
when the reactive power is within
limits
1:
reactive power alarm persists until
manually reset.
Reactive Capacitive
Power High Alarm Limit
kVAr
0
9’999
0
If the reactive capacitive power goes
over this limit, this will generate a
HIGH REACTIVE POWER alarm.
Capacitive Power Factor
alarm Limit
-
0
0.999
0
If the power factor is capacitive and
under this limit, then an CAPACITIVE
PF alarm will occur.
Inductive power factor
alarm Limit
-
0
0.999
0
If the power factor is inductive and
under this limit, then an INDUCTIVE
PF alarm will occur.
Power factor alarm
Duration
sec
0
255
30
When the power factor is outside limits,
the POWER FACTOR alarm will occur
after this timer.
Power Factor Alarm
Lock Enable
-
0
1
0
0:
compensation alarm disappears
when the power factor is within limits
1:
compensation alarm persists until
manually reset.
Current High Alarm Limit
A
0
5’000
0
If the current goes over this limit, this
will generate a HIGH CURRENT
alarm.
Current High Alarm
Duration
sec
0
255
30
When the active power is outside
limits, the active power alarm will occur
after this timer.
Current High Alarm Lock
Enable
-
0
1
0
0:
High current alarm disappears when
current is below limit
1:
High current alarm persists until
manually reset.
THD-V High Alarm Limit
%
0
50
0
If the THD of any voltage channel goes
over this limit, this will generate a
HIGH THD-V alarm.
THD-V t High Alarm
Duration
sec
0
255
30
When the THD-V goes over the limit,
the HIGH THD-V alarm will occur after
this timer.
THD-V High Alarm Lock
Enable
-
0
1
0
0:
HIGH THD-V alarm disappears
when the THD-V is below limit
1:
HIGH THD-V alarm persists until
manually reset.
20.2. ELECTRICAL PARAMETERS GROUP (continued)
Содержание DKM-411
Страница 31: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 31 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR...
Страница 34: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 34 4 8 1 PHASE 2 WIRE...
Страница 35: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 35 5 CONNECTION DIAGRAM...
Страница 41: ...DKM 411 User Manual Rev_01 Firmware V 1 0 K46D03 EN 41...