DKM-40
7 Kullanım Kılavuzu V-1.1
36
LED status register is 16 bits long. Each bit shows the status of one led.
BIT NO:
DESCRIPTION
0
k/M (Kilo/Mega)
1
Relay
2
Frequency (Hz)
3
Total (Sum)
4
Demand
5
MAX
6
MIN
7
kVArh
8
kWh
9
cos
10
kVA
11
kVAr
12
kW
13
Amperes (A)
14
Phase-Phase Voltages (VLL)
15
Phase-Neutral Voltages (VLN)
Button status register is 16 bits long. Each bit shows the status of one button.
BIT NO:
DESCRIPTION
0
Set (Menu) button pressed
1
Set (Menu) button long pressed
2
Set (Menu) button very long pressed
3
Up Arrow button pressed
4
Up Arrow button long pressed
5
Up Arrow button very long pressed
6
Down Arrow button pressed
7
Down Arrow button long pressed
8
Down Arrow button very long pressed
9
Digital Input Status (1:N.O. 0:N.C.)
10
-
11
-
12
-
13
-
14
-
15
-