DKM-40
7 Kullanım Kılavuzu V-1.1
25
If any of the 4 relay functions explained in chapter 4.16 is set to 2 (kWh pulse) or 3 (kVArh
pulse) then the relay output will provide energy increment pulses conformally to below
settin
gs. When pulse output is set, other 3 relay functions are “don’t care”. The relay will
function as a pulse output. kWh pulse output has priority. Thus if the output is set for both
kWh and kVArh then it will function as kWh.
This parameter determines the amount of
kWh (or kVArh) for 1 pulse output.
The factory set value is 1.000 kW per
pulse.
The adjustment range is from 0.001 to
10.000 kW (or kVArh)
Standart fabrika çıkış değeri 1.000 kWh
veya kVArh’dır.
.
This parameter determines the pulse active
period.
The factory set value is 0.20 sec (200
milisecond).
Adjustment range is 0.01sec to 9.99 sec.
This parameter determines the minimum
rest duration between two pulses.
The factory set value is 0.20 sec (200
milisecond).
Adjustment range is 0.01sec to 9.99 sec.
4.19 ENERGY PULSE OUTPUT (kWh, kVArh) PARAMETERS