13
This parameter sets the primary rating of
current transformers.
Current transformer secondary rating
should be 5 Amps.
The factory set default value is 500/5A.
Acceptable values are 5/5A to 5000/5A.
This parameter sets the ratio of voltage
transformers.
All voltage and power measurements will
be displayed after multiplication with this
parameter.
The factory set default value is 1.0
Acceptable values are 0.1 to 200.0
4.8 SETTING THE VOLTAGE TRANSFORMER RATIO
4.7 SETTING THE CURRENT TRANSFORMER RATIO