DKG-108 User Manual V-1.0
(10.08.2011)
-26-
DISPLAY
DESCRIPTION
MIN
STD MAX
CAPACITIVE REACTIVE POWER
HIGH LIMIT
If the reactive power is capacitive and
above this limit, it will generate an
excess kVAr capacitive alarm.
If this limit is set to zero then the alarm is
not monitored.
0
kVAR
0
kVAR
6500
kVAR
INDUCTIVE REACTIVE POWER HIGH
LIMIT
If the reactive power is inductive and
above this limit, it will generate an
excess kVAr inductive alarm.
If this limit is set to zero then the alarm is
not monitored.
0
kVAR
0
kVAR
6500
kVAR
REACTIVE POWER ALARM DELAY
For any kVAr alarm, the limit must be
overridden during this period.
0 sec
30 sec 200
sec
REACTIVE POWER ALARM
FUNCTION
0
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
1
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
2
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
0
0
3