DKG-108 User Manual V-1.0
(10.08.2011)
-21-
DISPLAY
DESCRIPTION
MIN
STD MAX
REGULATION LIMIT FOR C-/C+ LEDS
This is the difference from the target
cosø
for C-,OK,C+ leds to turn on.
1 %
5 %
20 %
NOMINAL VOLTAGE
This is the phase-to-neutral voltage for
which bank ratings are defined.
70 V
220V
9999 V
NOMINAL FREQUENCY
This is the network frequency for which
bank ratings are valid.
30 Hz
50 Hz
400 Hz
NUMBER OF FIXED STEPS
This number of steps, starting from the
step-1 will be always active.
0
0
4
TURN_ON ALERT TIMER
After a new step combination has been
determined, the leds of steps to be
modified start to flash and only after
expiration of this timeout the steps are
activated.
During this timer no new step
combination is calculated.
0 sec
3 sec
2000
sec
TURN_OFF ALERT TIMER
After a new step combination has been
determined, the leds of steps to be
modified start to flash and only after
expiration of this timeout the steps are
deactivated.
During this timer no new step
combination is calculated.
0 sec
1 sec
2000
sec