DKG-108 User Manual V-1.0
(10.08.2011)
-25-
DISPLAY
DESCRIPTION
MIN
STD MAX
ACTIVE POWER HIGH LIMIT
If the active power is above this limit, it
will generate an excess kW alarm.
If this limit is set to zero then the alarm is
not monitored.
0 kW
0kW
6500
kW
ACTIVE POWER LOW LIMIT
If the active power is below this limit, it
will generate a low kW alarm.
If this limit is set to zero then the alarm is
not monitored.
0 kW
0 kW
6500
kW
ACTIVE POWER ALARM DELAY
For any kW alarm, the limit must be
overridden during this period.
0 sec
30 sec 200
sec
ACTIVE POWER ALARM FUNCTION
0
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
1
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
2
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
0
0
3