D-500L Firmware V-5.8
K35D03-EN - 82 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Genset Low Frequency
Warning Limit
%
F-100 F+100
V-15%
If the genset frequency goes under this
limit when feeding the load, this will
generate a
GENSET LOW
FREQUENCY
warning.
Genset Low Frequency
Shutdown Limit
%
F-100 F+100
F-20%
If the genset frequency goes under this
limit when feeding the load, this will
generate a
GENSET LOW
FREQUENCY
shutdown alarm and the
engine will stop.
Genset High Frequency
Warning Limit
%
F-100 F+100 F+15%
If the genset frequency goes over this
limit when feeding the load, this will
generate a
GENSET HIGH
FREQUENCY
warning.
Genset High Frequency
Shutdown Limit
%
F-100 F+100 F+20%
If the genset frequency goes over this
limit when feeding the load, this will
generate a
GENSET HIGH
FREQUENCY
shutdown alarm and the
engine will stop.
Genset Frequency Fail
Timer
sec
0
10
1
If the genset frequency goes outside of
the limits during this timer, a genset
frequency fault will occur.
Low Battery Voltage
Warning Limit
V-DC
5.0
35.0
12.0
If the battery voltage falls below this
limit, this will generate a
LOW
BATTERY
warning.
Low Battery Voltage
Shutdown Limit
V-DC
5.0
35.0
9.0
If the battery voltage falls below this
limit, this will generate a
LOW
BATTERY
shutdown
alarm and the
engine will stop.
High Battery Voltage
Warning Limit
V-DC
5.0
35.0
29.0
f the battery voltage goes over this limit,
this will generate a
HIGH BATTERY
warning.
High Battery Voltage
Shutdown Limit
V-DC
5.0
35.0
30.0
If the battery voltage goes over this
limit, this will generate a
HIGH
BATTERY
shutdown
alarm and the
engine will stop.
Battery Voltage Fail
Timer
sec
0
10
3
If the battery voltage goes outside of the
limits during this timer, a battery voltage
fault will occur.
Genset Voltage
Unbalance Limit
%
0
100
0.0
If any genset phase voltage differs from
the average more than this limit, it will
generate a Voltage Unbalance fault
condition. The action taken upon fault
condition is programmable.
If this parameter is set to 0.0 then
voltage unbalance is not monitored
Genset Voltage
Unbalance Action
-
0
3
0
0:
no action
1:
shutdown alarm
2:
loaddump alarm
3:
warning
16.2. ELECTRICAL PARAMETERS GROUP (continued)
Содержание D Series
Страница 30: ...D 500L Firmware V 5 8 K35D03 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 31: ...D 500L Firmware V 5 8 K35D03 EN 31 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 32: ...D 500L Firmware V 5 8 K35D03 EN 32 4 7 2 PHASE 3 WIRE DELTA 2 CTs L1 L2 4 6 3 PHASE 3 WIRE DELTA 2 CT L1 L3 ...
Страница 33: ...D 500L Firmware V 5 8 K35D03 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...