D-500L Firmware V-5.8
K35D03-EN - 34 -
The same unit provides different functionalities through parameter setting. Thus a single stock item will
fulfill various duties, minimizing stock cost.
CTs may be placed at alternator or load busbars. The CT location selection is configured with
Controller
Configuration > CT Location
parameter.
When CTs are located at the alternator side, them mains current and power parameters will not be
displayed.
When CTs are located at load side, then both mains and genset currents and power parameters will be
displayed, based on contactor positions.
Please review AMF functionality connection diagrams for CT connection details.
When AMF functionality is selected, the unit will monitor mains voltages, provide mains and genset
contactor control, run the engine and provide engine and alternator instrumentation and fault monitoring.
The unit features both MPU and J1939 CANBUS inputs. Thus both mechanical and electronic engines
are supported.
The unit provides control outputs for both contactors and motorized circuit breakers.
When ATS functionality is selected, the unit will monitor mains voltages, provide mains and genset
contactor control and issue a Remote Start signal to the engine controller. It will provide alternator
instrumentation and fault monitoring.
Engine instrumentation and protection will be insured by the engine controller.
When the Remote Start functionality is selected, the unit will wait for a Remote Start signal from external
controller. Upon reception of this signal, it will run the engine, and provide engine and alternator
instrumentation and fault monitoring. The genset contactor/MCB control functionality will be available.
The unit features both MPU and J1939 CANBUS inputs. Thus both mechanical and electronic engines
are supported.
5.1. CT LOCATION SELECTION
5.4. REMOTE START FUNCTIONALITY
5.3. ATS FUNCTIONALITY
5.2. AMF FUNCTIONALITY
5. FUNCTIONALITIES
Содержание D Series
Страница 30: ...D 500L Firmware V 5 8 K35D03 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 31: ...D 500L Firmware V 5 8 K35D03 EN 31 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 32: ...D 500L Firmware V 5 8 K35D03 EN 32 4 7 2 PHASE 3 WIRE DELTA 2 CTs L1 L2 4 6 3 PHASE 3 WIRE DELTA 2 CT L1 L3 ...
Страница 33: ...D 500L Firmware V 5 8 K35D03 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...