D-500L Firmware V-5.8
K35D03-EN - 85 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Mains Contactor Timer
sec
0
600
0.5
This is the period after the generator
contactor has been deactivated and
before the mains contactor has been
activated.
Mains MCB Close Pulse
sec
0
10
0.5
After the mains MCB_undervoltage coil
is energized and mains
MCB_undervoltage coil timer is
elapsed, the mains MCB_close relay
will be activated during this period.
Review
chapter “
Motorized Circuit
Breaker Control
” for more details.
Mains MCB Open Pulse
sec
0
10
0.5
The mains MCB_open relay will be
activated during this period.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
Mains MCB Under
Voltage Coil Timer
sec
0
10
0.5
The mains MCB_undervoltage coil is
energized during this period before the
mains MCB_close relay is activated.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
MCB Alarm Level
-
0
1
0
0:
shutdown alarm
1:
loaddump alarm
Mains MCB Fail Timer
sec
0
600
2.0
If a mains MCB feedback input is
defined and if the mains MCB fails to
change position before the expiration of
this timer, then a fault condition occurs.
Mains Phase Order
Check Enable
-
0
1
0
0:
mains phase order checking disabled
1:
if mains phase order is faulty, then a
warning is given and mains contactor
deenergized.
Genset Contactor Timer
sec
0
600
0.5
This is the period after the mains
contactor has been deactivated and
before the genset contactor has been
activated.
Genset MCB Close Pulse
sec
0
10
0.5
After the genset MCB_undervoltage coil
is energized and genset
MCB_undervoltage coil timer is
elapsed, the genset MCB_close relay
will be activated during this period.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
Genset MCB Open Pulse
sec
0
10
0.5
The genset MCB_open relay will be
activated during this period.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
Genset MCB Under
Voltage Coil Timer
sec
0
10
0.5
The genset MCB_undervoltage coil is
energized during this period before the
genset MCB_close relay is activated.
Review chapter “
Motorized Circuit
Breaker Control
” for more details.
16.2. ELECTRICAL PARAMETERS GROUP (continued)
Содержание D Series
Страница 30: ...D 500L Firmware V 5 8 K35D03 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 31: ...D 500L Firmware V 5 8 K35D03 EN 31 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2 ...
Страница 32: ...D 500L Firmware V 5 8 K35D03 EN 32 4 7 2 PHASE 3 WIRE DELTA 2 CTs L1 L2 4 6 3 PHASE 3 WIRE DELTA 2 CT L1 L3 ...
Страница 33: ...D 500L Firmware V 5 8 K35D03 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...