gForce Ultra IOM
93
dap4 Settings for Ultra Units
h.
Digital Input:
Dirty Filter Switch Channel:
Action:
Delay:
Status:
ID8 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
i.
Digital Input:
Humidifier Fault Sw Channel:
Action:
Delay:
Status:
ID9 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
j.
Digital Input:
Energy Saver Switch Channel:
Action:
Delay:
Status:
ID10 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
k.
Digital Input:
Hi Condensation Sw Channel:
Action:
Delay:
Status:
ID11 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
l.
Digital Input: Fan Overload (Fan Fail) Channel:
Action:
Delay:
Status:
ID12 (Default)
Open (When Ziehl-Abegg fans are used)
Closed (When ebm papst fans are used)
5s (Default)
Open
Info Only Based on Sw State
m.
Digital Input:
Opt Alarm #1 Switch Channel:
Action:
Delay:
Status:
ID13 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
n.
Digital Input:
Opt Alarm #2 Switch Channel:
Action:
Delay:
Status:
ID14 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
o.
Digital Input:
Opt Alarm #3 Switch Channel:
Action:
Delay:
Status:
ID15 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State
p.
Digital Input: Opt Alarm #4 Switch
Channel:
Action:
Delay:
Status:
NOTE: Variable Compressor Fault
ID16 (Default)
Closed (Default)
5s (Default)
Open (Default)
q.
Digital Input:
Floor Water Switch Channel:
Action:
Delay:
Status:
ID17 (Default)
Closed (Default)
5s (Default)
Open
Info Only Based on Sw State