gForce Ultra IOM
60
Finish charging by slowly opening the valve on the refrigerant manifold set to meter liquid refrigerant
into the low side of the system, with the compressor operating at maximum speed, make sure to obtain
the required sub-cooling and verify superheat shown in the table below. Use a liquid charging adapter
to prevent liquid refrigerant from entering the compressor. The unit should be allowed to stabilize for
15 to 20 minutes to verify key measurements.
Table 14 Refrigerant Charge Valves
Function
R-410A Conditions
Discharge Pressure
322 PSIG (2220 kPa) minimum
Liquid Line Pressure
290 to 390 PSIG (2000 to 2687 kPa)
Liquid Line Temperature
85
to 100
F (29.4
to 37.8
C)
Suction Pressure
103 to 130 PSIG (710 kPa to 896 kPa)
Suction Saturated Temperature
33
to 45°F (0.56 to 7.22°C)
Subcooling
8
to 15°F (-13.33
to -9.44°C)
Differential Temperature - Depending on ambient conditions,
at compressor’s maximum speed
Superheat
8
to 18°F (-13.33
to -7.78°C)
Differential Temperature
Measure the superheat at the compressor suction line at least 6 inches (152 mm) away from the
compressor. Compare suction pressure and temperature reading between the dap4 and the manifolds.
If the difference between the manifold reading and dap4 reading is more than 5%, check for the EEV
wiring and any possible alarms on dap4, or EEV driver. Measure sub-cooling at the liquid line.
When charging is complete, add the correct amount of oil. This procedure must be conducted with the
system running at high load (compressor at full speed).
5.8.2. Additional Oil
When charging is complete, add the correct amount of oil to each circuit. In installations with good oil
return and line runs up to 50 ft (15 m), no additional oil is required. If installation lines exceed 50 ft (15
m), additional oil needs to be added. Add 1 or 2% of the total system refrigerant charge (in weight) can
be used to roughly define the required oil top-up quantity.
Top-up the oil while the compressor is idle. Use any accessible connector on the compressor suction
line and a suitable pump. ALWAYS use clean original Danfoss POE oil 160SZ or equivalent from new
cans.
After charging, verifying sub-cooling and oil level.
Close the valve on the refrigerant manifold gauge set and close the service valve on the refrigerant
tank and disconnect the refrigerant manifold gauge set.