background image

Data Aire’s dap4 Modbus TCP/IP 

 

Document:

 

600

000

961

 

version

 

4.0

 

11

 

 

Point

 

Index

 

Description

 

Read/

Write

 

Variable

 

Name

 

Data

 

Type

 

Modbus

 

TCP/IP

 

128 

State of U14 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* 

Unit14_status 

35129 

129 

State of U15 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* 

Unit15_status 

35130 

130 

State of U16 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* 

Unit16_status 

35131 

Dehumidify mode is running 

Dehum_On 

10002 

Humidifier is running 

Hum_On 

10003 

Energy saver is running 

Engy_On 

10004 

Cooling inhibit from Zone Master* 

Cool_Inhibit 

10005 

Heat inhibited due to alarm condition 

Heat_Held 

10006 

Humidifier stopped due to alarm R 

Humidifier_inhibit 

10007 

Dehum is inhibited 

Dehum_Inhibit 

10008 

reheat during dehum 

Rht_during_dehum 

10009 

Water under floor alarm 

Floor_Wtr_alm 

10010 

10 

No air flow alarm 

Air_Flow_alm 

10011 

11 

Dirty filter from digital input 

Filter_alm 

10012 

12 

Alarm from humidifier digital input* 

Humidifier_alm 

10013 

13 

Temperature of return air above firestat alarm set point 

Firestat_alm 

10014 

14 

One or more comps has short cycled 

Shortcycle_alm 

10015 

15 

Sensor is out of range 

Humidity_fail 

10016 

16 

Sensor is out of range 

Ret_Air_fail 

10017 

17 

Maintenance Schedule Due alarm 

Maint_alm 

10018 

18 

High pressure compressor 1 alarm 

C1_HP_alm 

10019 

19 

Low pressure compressor 1 alarm 

C1_LP_alm 

10020 

20 

High pressure compressor 2 alarm 

C2_HP_alm 

10021 

21 

Low pressure compressor 2 alarm 

C2_LP_alm 

10022 

22 

Smoke detected from digital input* 

Smoke_alm 

10023 

23 

No water flow alarm (stays high 5min longer if set to lockout)* 

Wtr_Flow_alm 

10024 

24 

Sensor is out of range 

Disch_Air_fail 

10025 

25 

Temperature of return air above alarm set point 

RA_Tmp_hi_alm 

10026 

26 

Temperature of return air below alarm set point 

RA_Tmp_lo_alm 

10027 

27 

Humidity above alarm set point 

Hum_hi_alm 

10028 

28 

Humidity below alarm set point 

Hum_lo_alm 

10029 

29 

Fan motor overload* 

Fan_Overload 

10030 

30 

Standby pump on: Check primary pump -Optional alarm. Pump failure input 
signal required* 

Stdby_Pump_On 

10031 

31 

Custom alarm #1 -Optional alarm. Custom message displayed* 

Cust_msg_Sw1 

10032 

32 

Custom alarm #2 -Optional alarm. Custom message displayed* 

Cust_msg_Sw2 

10033 

33 

Custom alarm #3 -Optional alarm. Custom message displayed* 

Cust_msg_Sw3 

10034 

34 

Custom alarm #4 -Optional alarm. Custom message displayed* 

Cust_msg_Sw4 

10035 

35 

Humidifier stopped due to custom alarm switch* 

HumSw_Inhibit 

10036 

36 

Heat inhibited due to custom switch alarm condition* 

Heat_inhibit 

10037 

Содержание dap4 touch

Страница 1: ...Data Aire dap4 Controller MODBUS TCP IP Protocol Integration Instructions Data Aire Inc 230 West BlueRidge Ave Orange CA 92865 Document number 600 000 961 November 2012 Revision 4 0...

Страница 2: ...Data Aire s dap4 Modbus TCP IP Document 600 000 961 version 4 0 2 Table of Content I Modbus TCP IP Setup Procedures for dap4 Ethernet Card page 3 II Modbus TCP IP BMS Points page 6...

Страница 3: ...hold the button on the card Now power on the dap4 controller Wait approximately 20 seconds until the status LED begins to blink red 3 times slowly After the first Red blink release the push button Aft...

Страница 4: ...d you will be taken to the following screen 9 Click the configuration tab on the left Then click on the BACnet tab across the top of the screen 10 This field is where you can change the settings for t...

Страница 5: ...ately 5 minutes for the IP address change to take 18 If there is no communication between the card and the BMS network the Push Button can be used to recall the factory setting configuration of the ca...

Страница 6: ...Sensor Calibration Optional chilled water temperature sensor required B10 R Ain_offs A 30012 12 Temperature setpoint for Energy saver chilled water R W EngSaver_Setpoint A 40013 13 Value of the analog...

Страница 7: ...re sensor 2 R Rack_T2 A 30049 49 Value of rack temperature sensor 3 R Rack_T3 A 30050 50 Temperature setpoint of the Zone Master R Master_Temp_Setpoint A 30051 1 Lower limit alarm of discharge air tem...

Страница 8: ...on optional alarm screen some also add function R Alarm4_txt I 35037 37 Comps 0 none 1 one 2 one UL 3 two 4 two UL 5 Four two circuit R Comp_sel I 35038 38 0 none 1 comp limited 2 twocomp limited 3 co...

Страница 9: ...7 NTC HT 8 50T90 9 10T170 R Ain_type I 35070 70 CW Fan speed controlled by BMS R W CW_Fan_Speed_bms I 45071 71 DX Fan speed controlled by BMS R W DX_Fan_Speed_bms I 45072 72 Maximum Fan speed of outpu...

Страница 10: ...an speed modulation percentage bases on output singal R Fan_Out I 35110 110 Setting of HP alarms hr before comp is locked out 1 disabled R W HP_Lockout_Cnt I 45111 111 Number of HP alarms C1 had withi...

Страница 11: ...Humidity_fail D 10016 16 Sensor is out of range R Ret_Air_fail D 10017 17 Maintenance Schedule Due alarm R Maint_alm D 10018 18 High pressure compressor 1 alarm R C1_HP_alm D 10019 19 Low pressure com...

Страница 12: ...l humidity cycling R Hum_Expect D 10050 51 Units of temperature 0 F 1 C R W USAshr_f_c D 00052 52 Lead compressor select 0 C1 1 C2 R Lead_Comp D 10053 53 Water valve direct or reverse acting R WtrVlv_...

Страница 13: ...fied 13 ONbyZM On by Zone Master Unit Off code 2 OFFbyALR off by alarm that controlled by ZM 3 OFFbyZM manually configured to off by ZM 4 OFFby BMS 5 OFFbySCH off by scheduler 6 STBbyZM send to standb...

Отзывы: